Technical Specifications
| Item | Specification |
|---|---|
| Product Name | Schneider Electric ATS480D88Y |
| Product Type | Soft Starter |
| Product Series | Altivar ATS480 |
| Rated Operational Current | 88 A (Normal Duty @ 40°C) |
| Heavy Duty Current | ~75 A |
| Supply Voltage (Power Circuit) | 208 – 690 V AC |
| Supply Frequency | 50 / 60 Hz |
| Control Supply Voltage | 110 – 230 V AC |
| Motor Power Range | ~22 kW to 75 kW (depending on voltage and duty) |
| Motor Type | 3-phase asynchronous motors |
| Control Method | Torque Control (TCS), voltage ramp start/stop |
| Starting Modes | Torque control start, voltage ramp |
| Stopping Modes | Freewheel stop, soft stop, DC injection braking |
| Built-in Protection | Motor overload, phase loss, locked rotor, thermal protection |
| Protection Rating | IP20 |
| Communication Interface | RJ45 (Modbus serial embedded) |
| Optional Communications | Modbus TCP, EtherNet/IP, PROFINET, CANopen, PROFIBUS (via modules) |
| Current Limiting | Up to 500% of rated current (up to ~700% transient) |
| Mounting Type | Panel / chassis mounting |
| Operating Temperature | -15°C to +60°C |
| Storage Temperature | -25°C to +70°C |
| Relative Humidity | 0–95% non-condensing |
| Altitude Derating | Required above 1000 m |
| Dimensions (H × W × D) | 290 × 190 × 247 mm |
| Weight | ~8.3 kg |
| Certifications | CE, UL, cULus, UKCA, CCC, RCM, EAC, DNV, ABS, BV |
FAQ
FAQ
Q1: What is the ATS480D88Y used for?
It is a soft starter used to control the starting and stopping of three-phase induction motors, reducing mechanical stress and limiting inrush current.
Q2: What motor size can it support?
It typically supports motors in the range of 22 kW to 75 kW depending on supply voltage and load conditions.
Q3: What is the main function of a soft starter like this?
It reduces voltage during motor start-up to limit current and torque, providing smoother acceleration compared to direct-on-line starting.
Q4: Does it support communication networks?
Yes, it has embedded Modbus RTU and supports optional communication modules such as PROFINET, EtherNet/IP, and CANopen.
Q5: What protection features are included?
It provides motor overload protection, phase failure detection, locked rotor protection, and thermal monitoring.
Q6: What are the dimensions and weight of the ATS480D88Y?
It measures 290 × 190 × 247 mm and weighs approximately 8.3 kg.
Q7: Can it be used outdoors?
No, it is rated IP20 and must be installed inside an electrical cabinet.
Q8: What is the control supply requirement?
It requires a 110–230 V AC control supply for operation.