GE IC200ALG326G Analog Current Output Module
GE IC200ALG326G Analog Current Output Module
GE IC200ALG326G Analog Current Output Module
GE IC200ALG326G Analog Current Output Module
Company Information
E-mail [email protected]
Mobile +8613950166376
Whatsapp +8613950166376
WeChat 13950166376

Manufacturer:GE

Product Number:IC200ALG326G

Product Type:Analog Current Output Module

Origin:USA

Dimensions:110 × 66.8 × 50 mm

Weight:0.20 kg


FAQ
Click to rate this post!
[Total: 0 Average: 0]

FAQ

Q1: What is the GE Fanuc IC200ALG326G used for?
The IC200ALG326G is an 8-channel analog current output module for the VersaMax I/O platform. It converts digital values from the PLC into analog current signals for controlling variable-speed drives, valve positioners, process controllers, and other industrial equipment.

Q2: What output ranges does the IC200ALG326G support?
The module supports 4–20 mA output by default. Installing the range-selection jumper changes the output range to 0–20 mA, allowing compatibility with different field devices.

Q3: How many analog output channels are available?
The IC200ALG326G provides eight single-ended analog current output channels arranged in a single output group, enabling simultaneous control of multiple field devices.

Q4: Does the IC200ALG326G require an external power supply?
Yes. An external 18–30 VDC power supply is required for the field-side output circuits. The module electronics receive operating power from the VersaMax backplane.

Q5: What diagnostic features are included?
The module reports a Loss of User Side Power fault if external field power is lost. It also includes OK and FLD PWR LEDs for quick visual indication of module and field power status.

Q6: What happens if communication with the PLC is interrupted?
A jumper allows users to choose whether the outputs hold their last values or switch to a predefined default value if backplane communication or PLC operation is interrupted, provided external field power remains available.

Q7: What does the “G” revision indicate?
The “G” suffix identifies the hardware revision of the IC200ALG326. Revision G remains fully compatible with VersaMax systems and primarily reflects manufacturing, quality, and lifecycle improvements without changing the module’s functional specifications.

Q8: What should be checked before replacing an IC200ALG326G module?
Before replacing the module, verify the VersaMax carrier compatibility, external 18–30 VDC field power supply, output range jumper, output default jumper, field wiring, PLC hardware configuration, and analog scaling parameters. Checking these items helps ensure reliable operation after installation.