Products Description




| Company Information | |||
| [email protected] | |||
| Mobile | +8613950166376 | ||
| +8613950166376 | |||
| 13950166376 |
Manufacturer:GE
Product Number:IC200PWR102H
Product Type:Expanded AC Power Supply Module
Origin:USA
Dimensions:128 × 50 × 50 mm
Weight:0.14 kg
FAQ
FAQ
Q1: What is the GE Fanuc IC200PWR102H used for?
The IC200PWR102H is an expanded AC power supply module for the VersaMax platform. It provides regulated 5 VDC and 3.3 VDC backplane power for CPUs, Network Interface Units (NIUs), and I/O modules installed in a VersaMax station.
Q2: What input voltage does the IC200PWR102H support?
The module accepts 85–132 VAC for 120 VAC systems (jumper installed) or 176–264 VAC for 240 VAC systems (jumper removed). It operates over an input frequency range of 47–63 Hz.
Q3: What output power does the IC200PWR102H provide?
The module supplies regulated 5 VDC and 3.3 VDC outputs with a maximum combined output current of 1.5 A. The 3.3 VDC output can deliver up to 1.0 A, while the remaining capacity is available for the 5 VDC output.
Q4: Can the IC200PWR102H be used as a secondary power supply?
Yes. Besides serving as the primary power supply for a VersaMax station, the IC200PWR102H can also be installed on a Power Supply Booster Carrier to provide supplemental backplane power for larger distributed I/O systems.
Q5: What protection features are included?
The module includes short-circuit protection and overload protection, helping protect both the power supply and connected VersaMax modules from abnormal operating conditions.
Q6: How is the input voltage selected?
A configuration jumper is used to select the operating voltage. Install the jumper for 120 VAC operation (85–132 VAC), and remove it for 240 VAC operation (176–264 VAC). Selecting the correct jumper position is essential for safe operation.
Q7: What does the “H” revision indicate?
The “H” suffix identifies the hardware revision of the IC200PWR102 power supply. Revision H remains fully compatible with VersaMax systems and primarily reflects manufacturing and reliability improvements without changing the module’s electrical performance.
Q8: What should be checked before replacing an IC200PWR102H module?
Before replacement, verify the VersaMax carrier compatibility, input voltage selection (120 VAC or 240 VAC), jumper position, total backplane power requirements, wiring connections, and the installed CPU or NIU configuration. These checks help ensure reliable power distribution and uninterrupted system operation.
Tags