GE IC200ALG326F Analog Output Module
GE IC200ALG326F Analog Output Module
GE IC200ALG326F Analog Output Module
GE IC200ALG326F Analog Output Module
Company Information
E-mail [email protected]
Mobile +8613950166376
Whatsapp +8613950166376
WeChat 13950166376

Manufacturer:GE

Product Number:IC200ALG326F

Product Type:Analog Output Module

Origin:USA

Dimensions:66.8 × 110 × 50 mm

Weight:0.16 kg


FAQ
Click to rate this post!
[Total: 0 Average: 0]

FAQ

Q1: What is the GE Fanuc IC200ALG326F used for?
The IC200ALG326F is used in VersaMax PLC systems to generate analog current signals for field devices such as control valves, variable speed drives, actuators, and process control equipment.

Q2: How many analog output channels does the IC200ALG326F provide?
The module provides 8 single-ended analog current output channels arranged in one output group.

Q3: What current output ranges are supported by the IC200ALG326F?
The module supports 4–20 mA output as the default range and can be configured for 0–20 mA output using a jumper setting.

Q4: What is the resolution of the IC200ALG326F?
The module provides 13-bit analog output resolution. For 4–20 mA operation, the resolution is approximately 2.5 µA per count, while 0–20 mA operation provides full 13-bit resolution.

Q5: Does the IC200ALG326F require an external power supply?
Yes. The output circuitry requires an external 18–30 VDC field power supply. The module also receives logic power from the VersaMax backplane.

Q6: What type of loads can be connected to the IC200ALG326F outputs?
The module can drive current-loop devices with resistive loads up to 800 Ω, including proportional valves, signal converters, controllers, and industrial actuators.

Q7: What diagnostic features are available on the IC200ALG326F?
The module provides field power monitoring through the FLD PWR LED and module power status through the OK LED. It also supports detection of loss of user-side field power.

Q8: What should be checked before replacing an IC200ALG326F module?
Before replacement, verify the VersaMax carrier compatibility, external 24 VDC field power supply, output current range configuration, jumper settings, field wiring, load resistance, and PLC hardware configuration to ensure correct operation.