Technical Specifications
| Parameter | Description |
|---|---|
| Product Model | INICT03A |
| Manufacturer | ABB Bailey |
| Product Series | INFI 90 / INFI-NET |
| Product Type | Infi-Net to Computer Transfer Module |
| Main Function | Transfers data and commands between the INFI-NET/Cnet network and a host computer |
| System Application | Distributed Control System (DCS) |
| Host Interface | RS-232-C or SCSI via IMMPI01 |
| RS-232-C Data Rate | User-selectable up to 19.2 kbaud |
| SCSI Data Rate | Up to 4 MB/s |
| Point/Tag Capacity | Up to 30,000 point definitions, depending on point types |
| Memory | 512 kB ROM; 2 MB RAM |
| Power Supply | +5 VDC |
| Current Consumption | Approx. 2 A |
| Power Consumption | Approx. 10 W |
| Mounting | One slot in standard INFI 90 Module Mounting Unit (MMU) |
| Related Interface Module | IMMPI01 Multifunction Processor Interface |
| Related Network Module | INNIS01 Network Interface Slave |
| Typical Configuration | INICT03A + INNIS01 + IMMPI01 |
| Operating Temperature | 0°C to +70°C |
| Dimensions | Approx. 37 × 317 × 178 mm |
| Product Weight | Approx. 0.54 kg |
FAQ
FAQ
Q1: What is the ABB Bailey INICT03A used for?
A: It is an Infi-Net to Computer Transfer Module used to connect an INFI 90 control network with a host computer.
Q2: Is the INICT03A an I/O module?
A: No. It is a communication/transfer module, not an analog or digital field I/O module.
Q3: What communication interfaces does the INICT03A support?
A: It supports RS-232-C and SCSI through the associated IMMPI01 interface module.
Q4: What is the maximum RS-232-C communication speed?
A: The RS-232-C interface is user-selectable up to 19.2 kbaud.
Q5: What is the SCSI communication speed?
A: The SCSI interface supports up to 4 MB/s.
Q6: How many point definitions can the INICT03A store?
A: It can store up to 30,000 point definitions, depending on the types of points configured.
Q7: What modules are normally used with the INICT03A?
A: A typical INICI03 configuration uses the INICT03A, INNIS01 and IMMPI01. The INNIS01 handles the network interface, while the IMMPI01 provides the host-computer interface.
Q8: What are the dimensions and weight of the INICT03A?
A: A commonly listed figure is approximately 37 × 31.7 × 17.8 cm with a weight of about 0.54 kg.