Manufacturer:Emerson
Product Number:KJ3002X1-BF1 12P1732X082
Product Type:RTD Card
Origin:USA
Dimensions:107 x 41 x 105 mm
Weight:1.13 kg
FAQ
Frequently Asked Questions (FAQ)
Q1: What RTD types are compatible with the KJ3002X1-BF1 card?
A1: The card supports Pt100, Pt200, Pt500, Ni120, Cu10, resistance, and user-defined RTDs with 2-, 3-, and 4-wire configurations.
Q2: Can this card be installed while the system is powered?
A2: Yes, under specific conditions outlined in the Zone 2 Installation Instructions, one unit at a time can be hot-swapped.
Q3: Is calibration required for the KJ3002X1-BF1?
A3: No. The card does not require calibration during operation or maintenance.
Q4: What is the A/D resolution of this RTD card?
A4: It uses a 16-bit analog-to-digital converter for high measurement resolution.
Q5: How is the open sensor detection handled?
A5: The card features open circuit and lead fault detection, typically responding within 1 second.
Q6: What diagnostic features does the card offer?
A6: Integrated diagnostics monitor sensor integrity, bus power, and signal health, with alerts shown in DeltaV diagnostics tools.
Q7: Does this card support redundant configurations?
A7: No, the KJ3002X1-BF1 is intended for simplex installations. For redundancy, other analog input cards in the DeltaV family should be used.
Q8: What is the power requirement for this card?
A8: The LocalBus requires 12 VDC at 160 mA, and each field input draws approximately 0.6 mA at 5.5 VDC.