Technical Specifications
| Parameter | Specification |
|---|---|
| Model | AAP135-S00/K4A00 |
| Number of Input Channels | 8, isolated channels |
| Input Signal | Contact ON/OFF, voltage pulse, current pulse (2-wire or 3-wire types) |
| Input Frequency | 0 to 10 kHz |
| Withstanding Voltage | Between input and system: 500 V AC for 1 minute |
| Minimum Input Pulse Width | 40 µs |
| Signal Level | Contact input: Open >100 kΩ, Close <200 Ω; Voltage/current pulse input: VH (high level): 3 to 24 V DC, VL (low level): -1 to 8 V DC |
| Shunt Resistance | Selectable: None/200/500/1000 Ω |
| Pull-up Resistance | 68 kΩ (12 V DC or 24 V DC) |
| Filter | Chattering elimination for dry contact signals (up to 10 Hz) |
| Data Update Period | 2 ms |
| Transmitter Power Supply | Selectable: 24 V DC/12 V DC |
| Limiter Value | 12 V DC ±10 %: 40 mA, 24 V DC ±10 %: 30 mA |
| Maximum Current Consumption | 300 mA (5 V DC), 400 mA (24 V DC) |
| Weight | 0.3 kg |
| External Connection | Pressure clamp terminal, KS cable, MIL connector cable |
| Dimensions (L x W x H) | 107.5 × 32.8 × 130 mm |
FAQ
FAQ
Q1: What is the input frequency range of the AAP135 Pulse Input Module?
A1: The input frequency range is from 0 to 10 kHz.
Q2: What types of input signals does the AAP135 module support?
A2: It supports contact ON/OFF, voltage pulse, and current pulse signals.
Q3: Can the AAP135 module be used in a dual-redundant configuration?
A3: Yes, the AAP135 module supports dual-redundant configuration.
Q4: What is the minimum input pulse width for this module?
A4: The minimum input pulse width is 40 µs.
Q5: What is the weight of the AAP135 module?
A5: The weight of the module is 0.3 kg.
Q6: What is the voltage range for the input pulse signals?
A6: The voltage pulse signal range is VH (high level): 3 to 24 V DC and VL (low level): -1 to 8 V DC.
Q7: Does the AAP135 module offer a filter for signal noise?
A7: Yes, it has a filter to eliminate chattering for dry contact signals up to 10 Hz.
Q8: What is the maximum current consumption of the module?
A8: The maximum current consumption is 300 mA at 5 V DC and 400 mA at 24 V DC.