Manufacturer:Honeywell
Product Number:CC-PAOH51 51410070-276
Product Type:Hart Analog Output Module
Origin:USA
Dimensions:63.5 x 124.46 x 307.34 mm
Weight:0.299 kg
FAQ
Frequently Asked Questions
Q1: How many analog output channels does the CC-PAOH51 module support?
A1: It supports 16 analog output channels (4-20 mA).
Q2: Does this module support redundancy?
A2: Yes, it supports redundancy using a redundant IOTA like CC-TAOX61.
Q3: Is HART communication supported on this module?
A3: Yes, the CC-PAOH51 supports HART protocol for status and configuration.
Q4: What happens to the output if the module fails?
A4: Each channel supports FAILOPT configuration—either hold last value or shed to a safe value (0 mA).
Q5: Is open wire detection available?
A5: Yes, open wire conditions are detected and indicated as soft failures.
Q6: What is the maximum resistive load supported?
A6: The module supports up to 800 ohms load with 22–28 VDC power supply.
Q7: What is the output response time?
A7: The output settles to within 1% of the final value within 80 milliseconds.
Q8: Does the module offer non-incendive output capability?
A8: Yes, it is suitable for Class 1, Division 2 environments with non-incendive outputs.