Yokogawa ADM52C-S2 Contact Output Module
Yokogawa ADM52C-S2 Contact Output Module
Yokogawa ADM52C-S2 Contact Output Module
Yokogawa ADM52C-S2 Contact Output Module
Company Information
E-mail [email protected]
Mobile +8613950166376
Whatsapp +8613950166376
WeChat 13950166376
Click to rate this post!
[Total: 0 Average: 0]

Technical Specifications

Parameter Specification
Model ADM52C-S2
Output Type Contact (Relay) Output
Number of Output Channels 16 channels
Contact Type SPST (Normally Open)
Rated Contact Voltage 30 V DC / 250 V AC
Rated Contact Current 2 A max
Isolation Relay contact isolated from system and channels
Output ON Delay ≤ 5 ms
Output OFF Delay ≤ 5 ms
Internal Power Supply 24 V DC
Installation Mounted on A2BA3D nest or N-IO base plate
Communication N-ESB Bus via NIU
Operating Temperature 0 to 55 °C
Storage Temperature -20 to 70 °C
Relative Humidity 5% to 95% RH (non-condensing)
Dimensions 130 × 100 × 30 mm
Weight 1.5 kg

FAQ
Click to rate this post!
[Total: 0 Average: 0]

Frequently Asked Questions (FAQ)

Q1: What type of output does the ADM52C-S2 module support?
A1: The module supports dry contact relay outputs, SPST type.

Q2: How many output channels are available on the ADM52C-S2?
A2: It has 16 individual output channels.

Q3: What is the maximum current the contact can handle?
A3: Each contact can handle up to 2 A.

Q4: Is the contact output isolated?
A4: Yes, all contact outputs are isolated from each other and from the internal system.

Q5: What is the output switching speed?
A5: Both ON and OFF delay times are within 5 milliseconds.

Q6: Can this module be used with HART communication?
A6: No, the ADM52C-S2 is a relay output module and does not support HART.

Q7: What is the operating voltage of the internal circuit?
A7: The internal power supply operates at 24 V DC.

Q8: What type of mounting is required for this module?
A8: It is designed to be mounted on the A2BA3D nest or a compatible N-IO base plate.