Welcome to NewPLC!

ABB SDCS-IOB-23 3ADT220090R0023 Digital Connection Board

ABB SDCS-IOB-23 3ADT220090R0023 Digital Connection Board

Release time:2025-05-19

Views:290

Payment Methods:T/T, PayPal, Western Union

Condition:New & In Stock

Shipping Port:Xiamen, China

Warranty:1 Year

Lead Time:1-3 Working Days

Certificate:COO

Courier partners:DHL, UPS, TNT, FedEx and EMS.

Business hours:7*24

Send Inquiry
Description
FAQ
Products Description
ABB SDCS-IOB-23 3ADT220090R0023 Digital Connection Board
ABB SDCS-IOB-23 3ADT220090R0023 Digital Connection Board
ABB SDCS-IOB-23 3ADT220090R0023 Digital Connection Board
ABB SDCS-IOB-23 3ADT220090R0023 Digital Connection Board
Company Information
E-mail [email protected]
Mobile +8613950166376
Whatsapp +8613950166376
WeChat 13950166376
Click to rate this post!
[Total: 0 Average: 0]

Technical Specifications

Parameter Details
Model Number SDCS-IOB-23
Ordering Code 3ADT220090R0023
Input Voltage Level 230 V AC
Digital Inputs 8 channels
Digital Outputs 8 channels
Input Type Optocoupler-isolated with filtering
Input Signal Range 0…40 V (LOW), 90…250 V (HIGH)
Input Resistance R1…R8 = 47 kΩ
Output Type Relay (K1-K5, K8) / Optocoupler (K6-K7) Isolated
Output Rating AC: ≤250 V~/3 A; DC: ≤24 V-/3 A or 115/230 V-/0.3 A
Output Protection MOV-protected (275 V)
Mounting External to DCS module, grounding required
Terminal Type Screw terminals, max wire size 4 mm²
Cable Length Limit X1X2: max 1.7 m; X1X3: max 0.5 m (EMC)
Chassis Grounding Conductive supports, mounting hole Ø 4.3 mm
Dimensions (L×W×H) 233.5 × 97.5 × 18.5 mm
Weight 0.35 kg

FAQ
Click to rate this post!
[Total: 0 Average: 0]

Frequently Asked Questions (FAQ)

Q1: How many digital I/O channels does the SDCS-IOB-23 have?
A1: It provides 8 digital inputs and 8 digital outputs.

Q2: What is the input voltage range?
A2: The input voltage is 90 to 250 V AC; low level is considered below 40 V.

Q3: Are the inputs electrically isolated?
A3: Yes, the inputs are galvanically isolated using optocouplers with filters.

Q4: What types of output drivers are used?
A4: Relay drivers (K1-K5, K8) and optocoupler drivers (K6-K7) are used.

Q5: What is the maximum output voltage and current?
A5: Up to 250 V AC / 3 A or 24 V DC / 3 A; certain ports support 230 V DC / 0.3 A.

Q6: Is grounding necessary for installation?
A6: Yes, proper grounding through conductive supports is required.

Q7: Is this module compatible with SDCS-CON-4?
A7: Yes, but the cable length limits (X1X2 = 1.7 m, X1X3 = 0.5 m) must be observed.

Q8: Which ABB systems support this board?
A8: It is used in ABB DCS500 and DCS800 drive systems.