Yokogawa SDV144-S53 Digital Input Module
Yokogawa SDV144-S53 Digital Input Module
Yokogawa SDV144-S53 Digital Input Module
Yokogawa SDV144-S53 Digital Input Module
Company Information
E-mail [email protected]
Mobile +8613950166376
Whatsapp +8613950166376
WeChat 13950166376
Click to rate this post!
[Total: 0 Average: 0]

Technical Specifications

Item Description
Model SDV144-S53
Number of Inputs 16 channels, module isolation
Input Signal Type No-voltage contact: ON ≤ 1 kΩ, OFF ≥ 100 kΩ
Input Current 6 mA ± 20% (External 24V DC, 0 Ω input)
Contact Rating 24 V DC (+20% / -10%), 10 mA or more
External Power Supply 24 V DC (+20% / -10%)
Power Supply Capacity 200 mA
Max Instant Input Voltage 30.0 V DC
Input Response Time Max 40 ms
Withstand Voltage 2 kV AC between input signals and system (16-point collective connection)
Current Consumption Max 290 mA (5 V DC); Max 140 mA (24 V DC)
External Connections Pressure clamp terminal, MIL cable, dedicated signal cable (AKB331)
Dimensions (W x H x D) 130 × 32.8 × 107.5 mm
Weight Approx. 0.36 kg (excluding signal cable interface adapter)

FAQ
Click to rate this post!
[Total: 0 Average: 0]

Frequently Asked Questions (FAQ)

Q1: How many input channels does the SDV144-S53 support?
A1: It supports 16 input channels with module-level isolation.

Q2: What is the standard input signal specification?
A2: The input is a no-voltage contact type: ON at ≤ 1 kΩ and OFF at ≥ 100 kΩ.

Q3: What is the input response time?
A3: The maximum response time is 40 milliseconds.

Q4: What is the withstand voltage capability of the module?
A4: It can withstand 2 kV AC between input lines and system when 16 points are connected collectively.

Q5: What are the external power requirements?
A5: Requires a 24 V DC supply with ±20% tolerance and a capacity of 200 mA.

Q6: What connection options are available?
A6: Connections can be made via pressure clamp terminal, MIL cable, or AKB331 signal cable.

Q7: Is dual-redundancy supported?
A7: Yes, SDV144 modules support dual-redundant configurations for enhanced reliability.

Q8: What are the physical dimensions and weight of the module?
A8: Dimensions are 130 x 32.8 x 107.5 mm, and the weight is approximately 0.36 kg.