Technical Specifications

Description Value
Number of channels 16
On board auxiliary power supply 42 V minimum, 55 V maximum
Propagation delay 7 mSec maximum
Contact bounce rejection Always rejects contact change of state < 3 mSec, Always accepts > 7 mSec
Closed contact output current 4 mA minimum, 8 mA maximum
Diagnostics Internal module operating faults, Ground Fault Detection
Dielectric isolation 1000 V AC/DC between channel and logic
Module power consumption 4.56 W typical, 4.75 W maximum
Operating temperature range 0°C to 60°C (32°F to 140°F)
Storage temperature range -40°C to 85°C (-40°F to 185°F)
Humidity 0% to 95% (non-condensing)
Dimensions 203 × 41 × 152 mm
Weight 0.68 kg

FAQ
Click to rate this post!
[Total: 0 Average: 0]

FAQ

1. What is the maximum number of channels supported by the Contact Input Module?

  • The module supports 16 channels.

2. What is the auxiliary power supply range of the Contact Input Module?

  • The on-board auxiliary power supply operates from 42 V minimum to 55 V maximum.

3. What is the maximum propagation delay for this module?

  • The maximum propagation delay is 7 milliseconds.

4. How is contact bounce rejection handled?

  • Contact changes lasting less than 3 mSec are rejected, while changes lasting more than 7 mSec are accepted.

5. What are the output current limits for closed contacts?

  • The output current for closed contacts is between 4 mA minimum and 8 mA maximum.

6. What diagnostics are available for this module?

  • It includes internal module operating fault detection and ground fault detection.

7. What is the dielectric isolation between channels and logic?

  • The module provides 1000 V AC/DC dielectric isolation.

8. What is the module’s power consumption?

  • The typical power consumption is 4.56 W, with a maximum of 4.75 W.