Technical Specifications
| Parameter | Specification |
|---|---|
| Product Model | ABB REU615C_D |
| Series | Relion® 615 Series |
| Function | Voltage Protection and Control Relay |
| Dimensions | 177 × 177 × 201 mm |
| Weight | 4.1 kg |
| Mounting | Flush-mounted |
| Degree of Protection (Front/Rear) | IP54 / IP20 |
| Auxiliary Voltage Supply (DC) | 24, 30, 48, 60, 110, 125, 220, 250 V DC |
| Auxiliary Voltage Supply (AC) | 100, 110, 120, 220, 240 V AC |
| Rated Frequency | 50/60 Hz ± 5% |
| Voltage Input Range | 60–210 V AC |
| Continuous Voltage Withstand | 240 V AC |
| Voltage Input Burden | < 0.05 VA |
| Current Inputs | 1/5 A |
| Thermal Withstand (1 s / continuous) | 500 A / 20 A |
| Binary Inputs | 12 (A config) / 8–14 (B config, optional) |
| Binary Outputs | 10 (A config) / 10–13 (B config, optional) |
| RTD Inputs (Optional) | 6 (B config only) |
| mA Inputs (Optional) | 2 (B config only) |
| Communication Protocols | IEC 61850, IEC 60870-5-103, Modbus, DNP3 |
| Ethernet Interfaces | RJ-45 / Fibre-optic LC/ST (optional) |
| Operating Temperature Range | -25°C to +55°C |
| Storage Temperature Range | -40°C to +85°C |
| Humidity | <93% RH, non-condensing |
| Altitude | Up to 2000 m |
| Environmental Compliance | RoHS, IEC 60255, EN 60255 |
| EMC Compliance | IEC 61000, EN 55011, IEEE C37.90 |