Manufacturer:Honeywell
Product Number:RM7800L1012
Product Type:Burner Control
Origin:USA
Dimensions:127 x 127 x 133 mm
Weight:0.83 kg
FAQ
FAQ
Q1: What type of burners is the RM7800L1012 suitable for?
A1: It is designed for single burner systems using gas, oil, or combination fuels that are automatically fired.
Q2: What is the maximum allowable power load the RM7800L1012 can handle?
A2: The maximum connected load is 2000 VA.
Q3: Does the RM7800L1012 support Modbus communication?
A3: Yes, it supports Modbus™ communication via an optional module (S7810M1003).
Q4: Can this burner control module be used in high-humidity environments?
A4: Yes, it can operate in environments with up to 85% relative humidity, non-condensing.
Q5: What is the flame failure response time range for this model?
A5: The flame failure response time ranges from 0.8 to 3.0 seconds, depending on the amplifier selected.
Q6: What are the mounting options available for the RM7800L1012?
A6: It can be mounted using either a Q7800A (panel mount) or Q7800B (wall/burner mount) subbase.
Q7: Is the RM7800L1012 compliant with safety standards?
A7: Yes, it is SIL 3 capable when configured properly and meets multiple agency approvals including UL, CSA, FM, and FCC.
Q8: Does it retain history and fault data after power loss?
A8: Yes, the RM7800L1012 features nonvolatile memory that preserves history files and status information during power interruptions.