Technical Specifications
| Parameter | Specification |
|---|---|
| Product Model | Honeywell RM7838A1014 |
| Series | 7800 SERIES |
| Voltage and Frequency | 120 Vac (+10/-15%), 50/60 Hz (±10%) |
| Power Dissipation | Relay Module: 10W max, Display Module: 3W max |
| Max Connected Load | 2000 VA |
| Fusing Requirement | 15A Fast Blow (Type SC or equivalent) |
| Flame Failure Response Time | 0.8 to 3.0 seconds (depending on amplifier used) |
| Operating Temperature | -40°C to +60°C |
| Storage Temperature | -40°C to +66°C |
| Relative Humidity | 85% RH, non-condensing |
| Vibration Resistance | 0.5G |
| Mounting Options | Q7800A (panel), Q7800B (wall or burner) |
| Dimensions | 127 x 127 x 133 mm |
| Weight | 0.74 kg (1 lb 13 oz) |
| Communication Interface | Modbus™, Data ControlBus™ (optional) |
| Display | Vacuum Fluorescent Display (2×20 characters) |
| Safety Certification | SIL3 capable, UL, CSA, FM, FCC Part 15 Class A, SwissRe |
| Required Components | Plug-in Flame Amplifier, ST7800A Purge Timer Card |