Technical Specifications
| Parameter | Specification |
|---|---|
| Model | SAI143-H03/A4D00 |
| Module Type | Analog Input Module, 16 channels, dual-redundant, module isolation |
| Input Signal | 4 to 20 mA |
| Permissible Input Range | 0 to 25 mA |
| Input Impedance (Power ON) | 250 Ω + Voltage drop in input protection circuit (0.45 V max, varies from 272.5 Ω at 20 mA to 362.5 Ω at 4 mA) |
| Input Impedance (Power OFF) | ≥500 kΩ |
| Rated Accuracy | ±16 µA (Input range 0.05 to 23 mA, Style code S3 or later) |
| Data Update Frequency | 40 ms |
| Temperature Drift | ±16 µA/10 °C |
| Transmitter Power Supply | 16.15 V min (at 20 mA), 26.4 V max (at 0 mA), Output current limit: 25 mA |
| 2/4-wire Setting | Individual channel setting via pins |
| Withstand Voltage | 1.5 kV AC between input signal and system for 1 minute (500 V AC for dedicated signal cable) |
| Maximum Current Consumption | 5 V system: 320 mA; 24 V system: 550 mA |
| External Connection | Dual-redundant pressure clamp terminal, MIL cable, dedicated signal cable |
| HART Communication | Yes, one HART device per channel; serial half duplex, 1200 ±2 bps, FSK modulation |
| PRM Support | Available |
| Transmitter Power ON/OFF Function | Available for all 16 channels simultaneously in 2-wire setting |
| Dimensions | 130 × 107.5 × 32.8 mm |
| Weight | 0.34 kg |
FAQ
FAQ
-
What is the maximum number of channels supported by SAI143-H03/A4D00?
The module supports 16 analog input channels with individual channel isolation and dual-redundancy. -
Can this module be connected to HART devices?
Yes, each channel supports one HART device, and the module has a single HART modem for concurrent communication. -
What is the rated accuracy for low current input ranges?
The rated accuracy is ±16 µA for input ranges from 0.05 to 23 mA (Style code S3 or later). -
How does the module handle dual-redundancy?
The module can be configured in dual-redundant setup using two identical modules, with dual-redundant pressure clamp terminals. -
What is the update frequency of the input data?
Data is updated every 40 milliseconds. -
Is the transmitter power supply configurable per channel?
No, the transmitter power ON/OFF function is applied simultaneously to all 16 channels in 2-wire setting. -
What is the maximum voltage drop in the input protection circuit?
The maximum voltage drop is 0.45 V across the input protection circuit, depending on input current. -
What environmental limits should be considered for installation?
The module supports ISA Standard G3 and high-density installation, with ambient temperature range of -20 to 70 °C. Input channel usage may be restricted above 60 °C.