Technical Specifications
| Parameter | Specification |
|---|---|
| Model | Yokogawa SAI143-H53 S2 |
| Module Type | Analog Input Module (16 channels, 4–20 mA, module isolation) |
| Number of Input Channels | 16 channels |
| Rated Input Range | 4 to 20 mA |
| Permissible Input Range | 0 to 25 mA |
| Input Impedance (Power ON) | 250 Ω + Voltage drop in input protection circuit (0.45 V max) |
| Input Impedance (Power OFF) | ≥500 kΩ |
| Rated Accuracy | ±16 µA (Input range 1–23 mA) |
| Data Update Frequency | 40 ms |
| Temperature Drift | ±16 µA / 10 °C |
| Transmitter Power Supply | 16.15 V minimum (at 20 mA), 26.4 V maximum (at 0 mA), current limit: 25 mA |
| 2/4-Wire Setting | Individual channel setting via pins |
| Withstand Voltage | 1.5 kV AC (input signal vs. system, 1 min) |
| Maximum Current Consumption | 5 V system: 320 mA, 24 V system: 550 mA |
| Weight | 0.34 kg |
| Dimensions (W x H x D) | 130 × 107.5 × 32.8 mm |
| External Connection | Pressure clamp terminal / MIL cable / Dedicated signal cable |
| PRM Support | Available |
| Transmitter Power Supply ON/OFF Function | Available in 2-wire setting for all channels simultaneously |
| HART Communication | Supported (1 HART device per channel, 1200 bps, FSK modulation) |
FAQ
FAQ
-
Q1: What is the main application of the SAI143-H53 S2 module?
A1: The module is primarily used to input 4–20 mA analog signals from field devices in process automation systems and transmit accurate data to the ProSafe-RS system. -
Q2: Can the SAI143-H53 S2 module be used in a dual-redundant configuration?
A2: Yes, the module supports dual redundancy, but an additional module with the same specifications is required without option codes for dual-redundant setup. -
Q3: What is the effect of ambient temperature on the module performance?
A3: For SAI143-S ≤3 or SAI143-H ≤C at temperatures above 60°C, the number of usable channels may be restricted. Refer to the ProSafe-RS module guide for details. -
Q4: How is the transmitter power supplied and controlled?
A4: The module provides a 16.15–26.4 V power supply with a 25 mA current limit. In 2-wire settings, power to all channels can be switched ON/OFF simultaneously to reset alarms of Fire and Gas devices. -
Q5: What are the HART communication capabilities of this module?
A5: Each channel supports one HART device. The module uses serial half-duplex communication with a speed of 1200 bps and FSK modulation. -
Q6: What is the rated accuracy and input range?
A6: Rated accuracy is ±16 µA for input ranges of 1–23 mA. Style code S3 or later supports 0.05–23 mA with the same accuracy. -
Q7: What types of external connections are supported?
A7: Connections include pressure clamp terminals, MIL cables, and dedicated signal cables, with support for options like prevention pins or connector covers for flat ribbon cables. -
Q8: What is the weight and size of the module?
A8: The module weighs approximately 0.34 kg and has dimensions of 130 × 107.5 × 32.8 mm.