Welcome to NewPLC!

Honeywell FS-TPSU-2430 Field Termination Assembly Module

Honeywell FS-TPSU-2430 Field Termination Assembly Module

Release time:2025-08-19

Views:230

Payment Methods:T/T, PayPal, Western Union

Condition:New & In Stock

Shipping Port:Xiamen, China

Warranty:1 Year

Lead Time:1-3 Working Days

Certificate:COO

Courier partners:DHL, UPS, TNT, FedEx and EMS.

Business hours:7*24

Send Inquiry
Description
FAQ
Products Description
Honeywell FS-TPSU-2430 Field Termination Assembly Module
Honeywell FS-TPSU-2430 Field Termination Assembly Module
Honeywell FS-TPSU-2430 Field Termination Assembly Module
Honeywell FS-TPSU-2430 Field Termination Assembly Module
Company Information
E-mail [email protected]
Mobile +8613950166376
Whatsapp +8613950166376
WeChat 13950166376
Click to rate this post!
[Total: 0 Average: 0]

Technical Specifications

Parameter Specification
General Type Numbers FS-TPSU-2430, FC-TPSU-2430
Approvals CE, TUV, UL, CSA, FM
Safety Class Up to and including SIL3
MTBF Approx. 400,000 hours
Input Nominal Voltage 24 V DC
Input Voltage Range 18–36 V DC
Inrush Current ≤ 4 A
Output Voltage 30 V DC ± 0.25 V
Output Current 1 A (short-circuit proof)
Short-Circuit Current < 3.3 A
Ripple (0–30 MHz) < 0.1 Vrms
Regulation < 1% (load + line)
Transient Response Class C (NFC42801C)
Power-On Overshoot < 33 V
Overvoltage Protection 33 V
Long-Term Stability < 0.3% (after 30 min operation)
Efficiency > 75%
Switching Frequency > 25 kHz
Module Dimensions 150 × 70 × 62.3 mm
Weight 0.45 kg
DIN Rail TS32 / TS35 × 7.5, used rail length 151 mm
Fuse Rating 3.15 A, 5×20 mm, AC 250 V / DC 300 V, Manufacturer: Schurter, PN: 0001.2509
Termination Screw terminals, max wire size 2.5 mm² (AWG 14), strip length 7 mm, torque 0.5 Nm
Wiring Classification 80°C min.
Supply Requirements SELV compliant, Over-voltage class II up to 300 V AC
Isolation Voltage Input to output 2000 V AC (1 min), Input to relay contact 2000 V AC, Output to relay contact 2000 V AC
Operating Temperature -5°C to +70°C
Storage Temperature -40°C to +85°C
Cooling Natural convection
Altitude ≤ 2000 m
Alarm Functions Dual overvoltage protection, undervoltage detector with LED and read-back relay contact, restart only after 24 V DC removal
Mounting DIN rail, horizontal or vertical
Readback Relay Contact 36 V DC / 40 mA, 30 V AC / 40 mA

FAQ
Click to rate this post!
[Total: 0 Average: 0]

FAQ

  • What is the maximum output current of the FS-TPSU-2430?
    The maximum output current is 1 A, and the module is short-circuit proof.

  • What input voltage range is supported by this module?
    The module supports 18–36 V DC input voltage.

  • How is the module monitored for output voltage status?
    Output voltage is monitored via a local LED indicator and read-back relay contact.

  • What overvoltage protection does the FS-TPSU-2430 provide?
    It includes dual overvoltage protection and limits output voltage to 33 V.

  • Can the module be mounted vertically?
    Yes, the TPSU-2430 can be mounted on a DIN rail in either horizontal or vertical orientation.

  • What is the expected MTBF of this module?
    The module has an approximate MTBF of 400,000 hours.

  • What are the isolation voltage ratings for the module?
    Input to output, input to relay contact, and output to relay contact are rated at 2000 V AC for 1 minute.

  • What is the maximum ambient operating temperature for the FS-TPSU-2430?
    The module can operate safely up to +70°C.


Tags

Packing & Delivery

We will use wear-resistant cartons to seal the boxes, and take photos for your confirmation before sealing. We will pack the boxes only after confirmation.

For express delivery, we will use DHL, UPS, TNT, FedEx and EMS.

Please rest assured that we have a deep cooperation with express delivery companies and can ensure that your goods are delivered to you in good condition.


Leave Your Message