Products Description




| Company Information | |||
| sales@bid-procurement.com | |||
| Mobile | +8613950166376 | ||
| +8613950166376 | |||
| 13950166376 |
Manufacturer:Yokogawa
Product Number:ASI133-S50/SA3S0
Product Type:Current Input Module
Origin:Japan
Dimensions:130 x 107.5 x 32.8 mm
Weight:0.3 kg
FAQ
FAQ
-
What is the isolation voltage rating of the ASI133-S50/SA3S0?
The module provides 1500 V AC isolation between input channels and power supply, ensuring protection against ground loops and voltage surges. -
Can the module handle both 2-wire and 4-wire transmitters?
Yes, it supports both 2-wire and 4-wire 4–20 mA current transmitters with specified input resistance for each configuration. -
What is the accuracy of current measurement for this module?
The module achieves an accuracy of ±16 µA, suitable for precise industrial signal acquisition. -
What is the maximum input current the module can tolerate?
The module can safely accept input currents up to 22.5 mA without damage. -
How fast is the module’s response to input signal changes?
The step response time is 100 ms, and the data update period is 10 ms. -
Does the module provide power to 2-wire transmitters?
Yes, it supplies ≥16 V DC with a maximum output current of 20 mA. -
What are the recommended environmental conditions for operation?
It is designed for industrial environments with standard temperature and humidity ranges; avoid excessive vibration or moisture. -
What are the dimensions and weight of the module for installation planning?
The module measures 130 × 107.5 × 32.8 mm and weighs 0.3 kg, suitable for compact installation setups.