Welcome to NewPLC!

Email

sales@bid-procurement.com

WhatsApp

+8613950166376

Honeywell FC-IOBUS-CPIO Safety System I/O Bus from Controller Chassis to I/O Chassis

Honeywell FC-IOBUS-CPIO Safety System I/O Bus from Controller Chassis to I/O Chassis

Release time:2025-08-25

Views:193

Payment Methods:T/T, PayPal, Western Union

Condition:New & In Stock

Shipping Port:Xiamen, China

Warranty:1 Year

Lead Time:1-3 Working Days

Certificate:COO

Courier partners:DHL, UPS, TNT, FedEx and EMS.

Business hours:7*24

Send Inquiry
Description
FAQ
Products Description
Honeywell FC-IOBUS-CPIO Safety System I/O Bus from Controller Chassis to I/O Chassis
Honeywell FC-IOBUS-CPIO Safety System I/O Bus from Controller Chassis to I/O Chassis
Honeywell FC-IOBUS-CPIO Safety System I/O Bus from Controller Chassis to I/O Chassis
Honeywell FC-IOBUS-CPIO Safety System I/O Bus from Controller Chassis to I/O Chassis
Company Information
E-mail sales@bid-procurement.com
Mobile +8613950166376
Whatsapp +8613950166376
WeChat 13950166376

Manufacturer:Honeywell

Product Number:FC-IOBUS-CPIO

Product Type:I/O Bus from Controller Chassis to I/O Chassis

Origin:USA

Dimensions:32 x 150 x 127 mm

Weight:1 kg


FAQ
Click to rate this post!
[Total: 0 Average: 0]

FAQ

Q1: What is the role of the FC-IOBUS-CPIO in a Safety Manager system?
A1: It serves as the vertical I/O bus that transfers scan, test, and update signals between the Controller chassis and multiple I/O chassis.

Q2: How does the FC-IOBUS-CPIO support redundant system architectures?
A2: It provides separate IO bus1.x and IO bus2.x connections, ensuring proper pairing for redundant I/O bus configurations.

Q3: What termination requirements exist for this I/O bus?
A3: Each bus must be terminated using TERM-0001 for non-redundant setups or TERM-0002 for redundant configurations.

Q4: What type of connector is used on both ends of the bus?
A4: The bus is equipped with 34-pole latch connectors, ensuring secure and reliable attachment to CP and IO backplanes.

Q5: Can the FC-IOBUS-CPIO be used in both controller and extension cabinets?
A5: Yes, within controller cabinets it connects CPCHAS to IOCHAS, while extension cabinets require related models such as FS-IOBUS-CPX-x and FS-IOBUS-CPIOX for cabinet-to-cabinet connectivity.

Q6: How does the physical design of the cable support cabinet installations?
A6: Its 34-wire flat construction is optimized for vertical cabinet routing, minimizing space usage and maintaining signal integrity.

Q7: What are the mechanical dimensions and weight of the FC-IOBUS-CPIO?
A7: The assembly measures 32 × 150 × 127 mm and weighs approximately 1 kg.

Q8: Which chassis models are compatible with the FC-IOBUS-CPIO?
A8: It is designed for use between CPCHAS-0001/0002/0003 controller chassis and IOCHAS-0001S/R/0002S/R/0003S/R I/O chassis.


Tags

Packing & Delivery

We will use wear-resistant cartons to seal the boxes, and take photos for your confirmation before sealing. We will pack the boxes only after confirmation.

For express delivery, we will use DHL, UPS, TNT, FedEx and EMS.

Please rest assured that we have a deep cooperation with express delivery companies and can ensure that your goods are delivered to you in good condition.


Leave Your Message


Leave a message