Products Description




| Company Information | |||
| [email protected] | |||
| Mobile | +8613950166376 | ||
| +8613950166376 | |||
| 13950166376 |
Technical Specifications
| Parameter | Specification |
|---|---|
| Model Number | VE4002S1T2B |
| Product Type | Discrete Output Card |
| Manufacturer | Emerson Process Management |
| Series | DeltaV System |
| Function | Provides isolated discrete output channels for process control |
| Number of Channels | 16 isolated digital output channels |
| Output Type | Sourcing discrete (on/off) |
| Output Voltage | 24 VDC nominal |
| Output Current per Channel | 0.5 A maximum |
| Isolation | 250 V RMS channel-to-bus and channel-to-ground |
| Response Time | 5 ms typical |
| Module Power Requirement | 5 V DC (from system backplane) |
| Power Dissipation | 2 W typical |
| System Compatibility | DeltaV and CHARMs systems |
| Status Indicators | Individual LED indicators for output status |
| Built-in Diagnostics | Overcurrent detection and channel fault monitoring |
| Configuration | Software-configurable via DeltaV Explorer |
| Operating Temperature Range | -40°C to +70°C |
| Storage Temperature Range | -40°C to +85°C |
| Relative Humidity | 5% to 95% non-condensing |
| Mounting Type | Installed in DeltaV carrier or system baseplate |
| Certifications | CE, UL, CSA, ATEX approved |
| Dimensions | 107 × 41 × 105 mm |
| Weight | 0.5 kg |
FAQ
FAQ
Q1: What is the main function of the Emerson VE4002S1T2B module?
A1: The VE4002S1T2B provides 16 discrete output channels to control field devices such as actuators, solenoids, and indicator lights, enabling automated process control via the DeltaV system.
Q2: How many discrete channels does this module support?
A2: The module supports 16 independent digital output channels, each capable of controlling devices separately or in coordinated sequences.
Q3: What type of signals are output from this card?
A3: Each channel delivers a sourcing discrete output signal, typically at 24 VDC, suitable for standard industrial automation applications.
Q4: Is there electrical isolation on the output channels?
A4: Yes, each output channel is isolated up to 250 V RMS from the system bus and ground, which provides safety and minimizes electrical interference.
Q5: How can I monitor the status of each output channel?
A5: Each channel includes an LED indicator that displays the output state in real time, making diagnostics and troubleshooting straightforward.
Q6: Does the VE4002S1T2B offer fault detection?
A6: Yes, the module includes built-in diagnostics for overcurrent and channel faults, allowing the DeltaV system to detect and report abnormal conditions automatically.
Q7: How is the module configured and monitored?
A7: Configuration is performed using DeltaV Explorer software, which allows channel mapping, status monitoring, and integration of fault management within the control system.
Q8: What types of devices are commonly controlled by this module?
A8: It is typically used to control solenoid valves, relays, motor starters, indicator lights, and other discrete actuators in process automation systems.