Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | ABB |
| Product Family | CC-U |
| Model | CC-U/V |
| Order Code | 1SVR040008R1300 |
| Product Type | Universal voltage measuring / signal converter |
| Function | Voltage RMS measuring converter |
| Input Signal | Voltage RMS values, 0–600 V |
| Selectable Input Ranges | 0–100, 150, 250, 300, 400, 450, 550 or 600 V |
| Output Signal | 0 to ±55 mA / 0 to ±11 V |
| Supply Voltage | 24–48 V DC or 24 V AC |
| Electrical Isolation | 3-way electrical isolation |
| Measuring Principle | RMS measurement |
| Frequency Range | 0–600 Hz |
| Accuracy | ±0.5% of full scale |
| Response Time | Approx. 150 ms |
| Output Protection | Short-circuit proof |
| Connection | Pluggable terminals |
| Adjustment | Front gain and offset adjustment |
| Input Range Selection | Front rotary switch |
| Output Configuration | Lateral DIP switches |
| Status Indication | Green LED for supply voltage |
| Mounting | DIN rail |
| Operating Temperature | -20 to +60 °C |
| Storage Temperature | -40 to +80 °C |
| Dimensions (W × H × D) | 22.5 × 105 × 120 mm |
| Net Weight | 0.128 kg |
| Package Dimensions | Approx. 109 × 124 × 26 mm |
| Package Gross Weight | 0.156 kg |
FAQ
FAQ
Q1: What is the ABB CC-U/V 1SVR040008R1300?
A: It is a universal voltage measuring converter designed to convert AC/DC voltage RMS signals into standardized analog output signals.
Q2: What voltage range can it measure?
A: It can measure voltage RMS values from 0 to 600 V, with selectable input ranges from 0–100 V up to 0–600 V.
Q3: What output signals does the CC-U/V provide?
A: The configurable output range includes 0 to ±55 mA and 0 to ±11 V, with additional output ranges selectable through the DIP switches.
Q4: What power supply does 1SVR040008R1300 require?
A: This version operates from 24–48 V DC or 24 V AC.
Q5: Does the CC-U/V provide electrical isolation?
A: Yes. It provides three-way electrical isolation between the input, output and supply circuits.
Q6: What is the accuracy of the voltage converter?
A: The specified accuracy is approximately ±0.5% of full scale, with a typical response time of about 150 ms.
Q7: What are the dimensions and weight?
A: The unit measures approximately 22.5 × 105 × 120 mm and has a net weight of 0.128 kg (128 g).
Q8: How is the CC-U/V configured?
A: The input voltage range is selected using the front rotary switch, while the output range is configured through lateral DIP switches. Gain and offset can be adjusted from the front of the unit.