Technical Specifications
| Item | Specification |
|---|---|
| Model | Bently Nevada 330130-085-03-RU Extension Cable |
| Product Type | 3300 XL Armored Extension Cable |
| Cable Length | 8.5 m (27.9 ft) |
| Cable Type | Armored cable with enhanced connector protection (“03”) |
| Cable Material | 75 Ω triaxial, FEP-insulated |
| Capacitance | ~69.9 pF/m (21.3 pF/ft) typical |
| DC Resistance (Center Conductor) | Typical for 8.5 m armored cable |
| DC Resistance (Outer Conductor) | Typical for 8.5 m armored cable |
| Output Resistance | 50 Ω typical |
| Recommended Voltage | -17.5 Vdc to -26 Vdc (non-incendive system) |
| Operating Temperature | -40 °C to +85 °C industrial range |
| Field Wiring Support | 16–24 AWG shielded triad |
| Application | Connects 3300 XL Proximitor sensors/probes to monitoring modules |
| Dimensions | Cable length 8.5 m; assembly size varies with installation |
| Weight | ~0.9 kg (armored cable) |
| Special Designation | “RU” denotes Russian regional specification or compliance |
FAQ
FAQ
Q1: What is the purpose of the 330130-085-03-RU extension cable?
A1: It extends the connection between a 3300 XL proximitor sensor or probe and the monitoring system, providing armored protection and compliance with Russian regional requirements.
Q2: What does “330130-085-03-RU” signify?
A2: “085” indicates an 8.5 m cable length, “03” denotes an armored cable with enhanced connector protection, and “RU” indicates a Russian regional specification or compliance variant.
Q3: Is this cable compatible with standard 3300 XL systems?
A3: Yes, it is designed for use with the Bently Nevada 3300 XL proximity transducer system and is compatible with proximitor sensors and 8 mm probes.
Q4: What signal performance does this cable provide?
A4: It offers typical capacitance of ~69.9 pF per meter and an output resistance of 50 Ω, supporting accurate and reliable signal transmission.
Q5: What voltage range does the cable support?
A5: The cable operates with a DC supply in the range of approximately -17.5 Vdc to -26 Vdc in non-incendive industrial systems.
Q6: Why is the armored design important?
A6: The armored cable and enhanced connector protection improve mechanical durability and resistance to damage in demanding industrial environments.
Q7: What installation considerations should be made for this cable?
A7: The cable weighs about ~0.9 kg and is 8.5 m long; routing, support, and space planning should account for its length and weight.
Q8: What temperature conditions can the cable withstand?
A8: It can reliably operate in industrial temperature ranges from -40 °C to +85 °C.