Manufacturer:GE
Product Number:IC200MDL740G
Product Type:Discrete Output Module
Origin:USA
Dimensions:66.8 × 138 × 50 mm
Weight:0.20 kg
FAQ
FAQ
Q1: What is the GE Fanuc IC200MDL740G used for?
The IC200MDL740G is a 16-point discrete DC output module for the VersaMax I/O platform. It converts PLC output commands into electrical signals for controlling field devices such as relays, solenoid valves, contactors, indicator lamps, and other DC loads.
Q2: How many output channels does the IC200MDL740G provide?
The module provides 16 sourcing digital outputs, divided into two isolated groups of eight channels. This arrangement simplifies field wiring and allows separate power distribution for each group.
Q3: What output voltage and current does the IC200MDL740G support?
The module is designed for 12/24 VDC applications, with an operating voltage range of 10.2 to 30 VDC. Each output can deliver up to 0.5 A, with a maximum of 4 A per group and 8 A per module.
Q4: Does the IC200MDL740G require an external power supply?
Yes. The module requires an external 12/24 VDC field power supply to energize the output circuits. The PLC backplane supplies only the module electronics.
Q5: What types of field devices can be connected to this module?
The IC200MDL740G is suitable for driving solenoid valves, contactors, relays, pilot lights, alarms, and other 12/24 VDC industrial output devices.
Q6: Does the IC200MDL740G include output protection?
Yes. The module incorporates electronic short-circuit protection and thermal shutdown to help protect the outputs from overload and fault conditions, improving system reliability.
Q7: What does the “G” revision indicate?
The “G” suffix represents a hardware revision of the IC200MDL740 module. It maintains compatibility with VersaMax PLC systems while incorporating manufacturing and reliability improvements introduced during the product lifecycle.
Q8: What should be verified before replacing an IC200MDL740G module?
Before installation, verify the output voltage, load current requirements, field wiring, carrier base compatibility, power supply capacity, and PLC configuration. Confirming these parameters helps ensure reliable operation and prevents damage to connected equipment.