Welcome to NewPLC!

Email

sales@bid-procurement.com

WhatsApp

+8613950166376

GE IC693ALG390 Series 90-30 PLC Analog Voltage Output Module

GE IC693ALG390 Series 90-30 PLC Analog Voltage Output Module

Release time:2025-04-01

Views:144

Payment Methods:T/T, PayPal, Western Union

Condition:New & In Stock

Shipping Port:Xiamen, China

Warranty:1 Year

Lead Time:1-3 Working Days

Certificate:COO

Courier partners:DHL, UPS, TNT, FedEx and EMS.

Business hours:7*24

Send Inquiry
Description
FAQ
Products Description
GE IC693ALG390 Series 90-30 PLC Analog Voltage Output Module
GE IC693ALG390 Series 90-30 PLC Analog Voltage Output Module
GE IC693ALG390 Series 90-30 PLC Analog Voltage Output Module
GE IC693ALG390 Series 90-30 PLC Analog Voltage Output Module
Company Information
E-mail sales@bid-procurement.com
Mobile +8613950166376
Whatsapp +8613950166376
WeChat 13950166376

Manufacturer:GE Fanuc

Product Number:IC693ALG390

Product Type:Analog Voltage Output Module

Origin:USA

Dimensions:51 x 127 x 127 mm

Weight:0.34 kg


FAQ
Click to rate this post!
[Total: 0 Average: 0]

FAQs (Frequently Asked Questions)

Q1: What is the voltage output range of the IC693ALG390?

A1: The voltage output range of the IC693ALG390 is from –10V to +10V.

Q2: How is the accuracy of the IC693ALG390 module ensured?

A2: The module is factory calibrated, with an accuracy of ±5 mV at 25°C, and an offset of ±1 mV from 0 to 60°C.

Q3: Can the IC693ALG390 handle external power supplies?

A3: Yes, the IC693ALG390 can be powered by an external supply in the range of 18V to 30V DC.

Q4: What is the update rate of the module?

A4: The update rate for the module is approximately 5 milliseconds for both channels.

Q5: What kind of field wiring is recommended for the IC693ALG390?

A5: The module should be wired using twisted, shielded instrumentation cables to minimize noise and ensure good signal quality.

Q6: Can the IC693ALG390 hold its state when the PLC is stopped?

A6: Yes, the IC693ALG390 can be configured to either default to 0V or hold the last state when the PLC is stopped or reset.

Q7: What is the resolution of the analog output?

A7: The resolution of the analog output is 12 bits, effectively 13 bits (1 part in 8192).

Q8: How does the IC693ALG390 ensure noise immunity?

A8: The module uses electrical isolation between field wiring and the backplane and is designed to reject noise caused by external interference, ensuring accurate operation in noisy environments.