Manufacturer:GE
Product Number:IC693MDL655H
Product Type:Discrete DC Input Module
Origin:USA
Dimensions:127 × 38 × 140 mm
Weight:0.29 k
FAQ
FAQ
Q1: What is the GE Fanuc IC693MDL655H used for?
The IC693MDL655H is a 32-point 24 VDC digital input module for the GE Fanuc Series 90-30 PLC. It monitors ON/OFF signals from field devices such as push buttons, limit switches, proximity sensors, and selector switches, then transfers the input status to the PLC CPU for control and monitoring.
Q2: How many input channels does the IC693MDL655H provide?
The module provides 32 digital input points, organized into four isolated groups of eight inputs. Each group has its own common terminal, allowing flexible field wiring while maintaining electrical isolation between groups.
Q3: What input voltage does the IC693MDL655H support?
The module is designed for 24 VDC applications and accepts an operating input voltage range of 0 to 30 VDC. It supports both positive and negative logic, making it compatible with various industrial control systems.
Q4: What is the response time of the IC693MDL655H?
Both the ON and OFF response times are 2 milliseconds maximum, allowing reliable detection of standard industrial digital input signals.
Q5: What types of field devices can be connected to this module?
Typical devices include push buttons, emergency stop switches, selector switches, proximity sensors, limit switches, auxiliary contacts, and photoelectric sensors operating on 24 VDC.
Q6: Does the IC693MDL655H provide electrical isolation?
Yes. The module uses opto-couplers to provide 1500 VAC isolation between the field side and PLC logic, along with 250 VAC isolation between the four input groups, helping reduce electrical noise and improve system reliability.
Q7: What does the “H” revision indicate?
The “H” suffix identifies a later hardware revision of the IC693MDL655 module. It retains full compatibility with Series 90-30 PLC systems while incorporating manufacturing, certification, and reliability improvements during the product lifecycle.
Q8: What should be checked before replacing an IC693MDL655H module?
Before replacement, verify the Series 90-30 baseplate compatibility, input voltage, field wiring, logic configuration (positive or negative), connector cables, and PLC hardware configuration. Confirming these items helps ensure reliable installation and uninterrupted system operation.