GE IC694MDL231 PACSystems RX3i Discrete Input Module
GE IC694MDL231 PACSystems RX3i Discrete Input Module
GE IC694MDL231 PACSystems RX3i Discrete Input Module
GE IC694MDL231 PACSystems RX3i Discrete Input Module
Company Information
E-mail sales@bid-procurement.com
Mobile +8613950166376
Whatsapp +8613950166376
WeChat 13950166376

Manufacturer:GE Fanuc

Product Number:IC694MDL231

Product Type:Discrete Input Module

Origin:USA

Dimensions:34 x 145 x 140 mm

Weight:0.37 kg


FAQ
Click to rate this post!
[Total: 0 Average: 0]

Frequently Asked Questions (FAQ)

Q1: What voltage is required for the IC694MDL231 module?
A1: The module is designed for 24 VDC nominal input, with an operational range from 0 to +30 VDC.

Q2: How many input points are available on the IC694MDL231?
A2: The module provides 16 discrete input points.

Q3: Can the IC694MDL231 module detect low-level voltages?
A3: The minimum on-state voltage is 11 VDC, and the off-state threshold is 5 VDC, making it unsuitable for very low-level detection.

Q4: What is the typical current drawn by each input?
A4: Each input typically draws 7 mA at 24 VDC.

Q5: How is electrical isolation managed in this module?
A5: The module provides 250 VAC continuous isolation (1500 VAC for 1 second) between the field side and backplane, as well as between input groups.

Q6: Is input filtering configurable on the IC694MDL231?
A6: Yes, the module includes configurable filtering, with a default setting of 1 ms.

Q7: Are LED indicators provided for input status monitoring?
A7: Yes, there is one green LED indicator per input point, providing visual status indication.

Q8: Can this module be installed in any RX3i rack slot?
A8: It can be installed in any slot except the CPU and power supply slots.