GE IC695ALG312 PACSystems RX3i Isolated Thermocouple Input Module
GE IC695ALG312 PACSystems RX3i Isolated Thermocouple Input Module
GE IC695ALG312 PACSystems RX3i Isolated Thermocouple Input Module
GE IC695ALG312 PACSystems RX3i Isolated Thermocouple Input Module
Company Information
E-mail sales@bid-procurement.com
Mobile +8613950166376
Whatsapp +8613950166376
WeChat 13950166376

Manufacturer:GE Fanuc

Product Number:IC695ALG312

Product Type:Isolated Thermocouple Input Module

Origin:USA

Dimensions:34 x 145 x 140 mm

Weight:0.41 kg


FAQ
Click to rate this post!
[Total: 0 Average: 0]

Frequently Asked Questions (FAQ)

Q1: What types of thermocouples are supported by the IC695ALG312?
A1: The module supports J, K, T, E, R, S, B, N, and C type thermocouples.

Q2: Can I configure individual channels with different thermocouple types?
A2: Yes, each of the 12 channels can be individually configured with a specific thermocouple type or voltage input.

Q3: Is the module hot-swappable during operation?
A3: Yes, the IC695ALG312 supports Removal and Insertion Under Power (RIUP), allowing hot-swapping.

Q4: What is the resolution range for this module?
A4: Resolution varies based on filter settings and input type, ranging from 11.5 to 16 effective bits.

Q5: How does the module perform cold junction compensation?
A5: It uses external CJC sensors (IC695ACC600) installed on the terminal block. You can configure compensation from none, CJC1, CJC2, or both.

Q6: What happens if a thermocouple wire breaks or disconnects?
A6: The module detects open wire conditions and can report the fault via diagnostics and fault tables.

Q7: Are there onboard filters to reduce signal noise?
A7: Yes, the module supports programmable notch filters with selectable frequencies (2.3 Hz to 28 Hz).

Q8: Does the module support diagnostic or alarm signaling to the CPU?
A8: Yes, it provides configurable diagnostics, fault logging, and even interrupts to handle alarm events per channel.