Manufacturer:Schneider
Product Number:140ACI03000
Product Type:Analog Input Module
Origin:France
Dimensions:103.9 × 40.3 × 250 mm
Weight:0.3 kg
FAQ
FAQ for Schneider 140ACI03000 Analog Input Module:
Q1: What is the input voltage range for the Schneider 140ACI03000?
- A1: The module can handle 1…5 V DC input voltage.
Q2: What is the maximum allowable input current?
- A2: The maximum allowable input current is 25 mA.
Q3: Can this module handle both voltage and current inputs?
- A3: Yes, it supports both 1…5 V DC and 4…20 mA signals.
Q4: What is the resolution of the module?
- A4: The module has a 12-bit resolution.
Q5: What is the update time of this module?
- A5: The update time is 5 ms.
Q6: Is this module isolated from the bus?
- A6: Yes, it provides isolation between channels and the bus, rated at 1000 V DC.
Q7: What certifications does this module have?
- A7: It is FM Class 1 Division 2, cUL certified and complies with UL 508 and CSA C22.2 No 142.
Q8: Can I use this module in a high-temperature environment?
- A8: The operating temperature range is 0…60 °C, and the storage temperature range is -40…85 °C.
Q9: How do I troubleshoot faults in this module?
- A9: The module provides fault signaling via LEDs, including red LEDs for channel faults and broken wires.
Q10: What is the power consumption of this module?
- A10: The module requires 240 mA bus current and dissipates 2 W of power.
Tags
Packing & Delivery
We will use wear-resistant cartons to seal the boxes, and take photos for your confirmation before sealing. We will pack the boxes only after confirmation.
For express delivery, we will use DHL, UPS, TNT, FedEx and EMS.
Please rest assured that we have a deep cooperation with express delivery companies and can ensure that your goods are delivered to you in good condition.