Yokogawa AAI835-h00 Analog I/O Module

Yokogawa AAI835-h00 Analog I/O Module

Release time:2025-04-17

Views:250

Payment Methods:T/T, PayPal, Western Union

Condition:New & In Stock

Shipping Port:Xiamen, China

Warranty:1 Year

Lead Time:1-3 Working Days

Certificate:COO

Courier partners:DHL, UPS, TNT, FedEx and EMS.

Business hours:7*24

Send Inquiry
Description
FAQ
Products Description
Yokogawa AAI835-h00 Analog I/O Module
Yokogawa AAI835-h00 Analog I/O Module
Yokogawa AAI835-h00 Analog I/O Module
Yokogawa AAI835-h00 Analog I/O Module
Company Information
E-mail sales@bid-procurement.com
Mobile +8613950166376
Whatsapp +8613950166376
WeChat 13950166376

Manufacturer:Yokogawa

Product Number:AAI835-h00

Product Type:Analog I/O Module

Origin:Japan

Dimensions:107.5 × 32.8 × 130 mm

Weight:0.3 kg


FAQ
Click to rate this post!
[Total: 0 Average: 0]

Frequently Asked Questions (FAQ)

Q1: What type of signals does the AAI835-H00 module handle?
A1: The AAI835-H00 module handles analog current signals in the range of 4 to 20 mA for both input and output.

Q2: Is the AAI835-H00 module equipped with HART communication capability?
A2: Yes, it supports HART communication, including variable data collection via HART Command #3.

Q3: Are the input and output channels electrically isolated?
A3: Yes, each input and output channel is isolated from the system and from other channels.

Q4: What is the acceptable load resistance for the analog output?
A4: The module supports a load resistance of 0 to 750 Ω. For ambient temperatures between 60–70°C, it supports 200 to 750 Ω.

Q5: Can the module be used in dual-redundant configurations?
A5: Yes, it is designed to be used in dual-redundant configurations for improved reliability.

Q6: What happens when an open circuit is detected in an output channel?
A6: An open circuit condition is identified if the current falls below 0.65 mA, enabling fault detection.

Q7: What is the recommended transmitter power supply specification?
A7: The module supplies 15.0 V or higher at 20 mA and up to 29.3 V at 0 mA to support 2-wire transmitters.

Q8: Is the use of Zener barriers allowed with the AAI835-H00?
A8: No, Zener barriers are not allowed. Use isolation barriers when required in intrinsically safe applications.