Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Yokogawa |
| Model Number | F3LX02‑2N |
| Product Type | Yokogawa F3LX02‑2N FL‑net Interface Module |
| Network Standard | FL‑net (OPCN‑2) Ver. 2.00 (open FA Ethernet network) |
| Transmission Rates | 10 Mbps (10BASE‑T) / 100 Mbps (100BASE‑TX) |
| Network Protocols | IEEE802.3 CSMA/CD, UDP/IP, FA link protocol, ICMP, ARP |
| Maximum Nodes Supported | 254 nodes per network |
| Cyclic Transmission | Area 1: 512 words; Area 2: 8192 words |
| Message Transmission | Up to 1024 bytes per message |
| Maximum Segment Length | 100 m (standard Ethernet cable) |
| Maximum Cascade Stages | 2 stages @ 100Mbps; 4 stages @ 10Mbps |
| Power Consumption | ≤ 330 mA @ supply voltage (internal PLC bus) |
| Compatible CPU Modules | FA‑M3 CPU modules (various F3SP series) |
| Operating Environment | Standard industrial PLC environment |
| Mounting | PLC rack / FA‑M3 base unit |
| Dimensions | 28.9 mm (W) × 100 mm (H) × 83.2 mm (D) |
| Weight | Approx. 100 g |
FAQ
FAQ
Q1. What is the F3LX02‑2N module used for?
It is an FL‑net (OPCN‑2) interface communication module for Yokogawa FA‑M3 PLC systems supporting multi‑vendor high‑speed data links.
Q2. What network standards does this module support?
It supports 10BASE‑T and 100BASE‑TX Ethernet at up to 100 Mbps.
Q3. How many nodes can connect using F3LX02‑2N on a network?
Up to 254 network nodes can be connected.
Q4. What communication protocols does it handle?
It handles IEEE802.3 Ethernet with UDP/IP, FA link protocol, ICMP, and ARP.
Q5. Can this module send both cyclic and message data?
Yes; it supports cyclic data transmission and message transmission up to 1024 bytes.
Q6. How far can Ethernet cable run with this module?
Typical maximum segment length is about 100 meters without repeaters.
Q7. What size is the F3LX02‑2N module?
The external dimensions are approximately 28.9 × 100 × 83.2 mm.
Q8. Is the module lightweight and suitable for PLC racks?
Yes; it weighs about 100 g and fits standard PLC module mounting.