Manufacturer:GE
Product Number:IC200MDL740E
Product Type:Discrete DC Output Module
Origin:USA
Dimensions:110 × 66.8 × 50 mm
Weight:0.23 kg
FAQ
FAQ
Q1: What is the GE Fanuc IC200MDL740E used for?
The IC200MDL740E is a 16-point positive logic discrete DC output module designed for VersaMax PLC systems. It switches 12/24 VDC loads such as relays, solenoid valves, contactors, pilot lights, and other industrial actuators.
Q2: How many output channels does the IC200MDL740E provide?
The module provides 16 digital output points arranged in one output group. The CPU or Network Interface Unit (NIU) transfers 16 bits of output data to the module for field device control.
Q3: What voltage and current ratings are supported?
The IC200MDL740E operates with an external 10.2–30 VDC supply (12/24 VDC nominal). Each output can switch up to 0.5 A, making it suitable for a wide variety of industrial DC loads.
Q4: Does the IC200MDL740E require an external power supply?
Yes. An external 10.2–30 VDC field power supply is required to power the output loads. The VersaMax backplane powers only the module electronics, while the external supply powers the connected field devices.
Q5: What diagnostic indicators are available?
The module includes an OK LED to indicate backplane power, a FLD PWR LED to indicate field power availability, and individual LEDs for each output point to display ON/OFF status.
Q6: Does the IC200MDL740E include output protection?
The module does not contain internal output fuses. External suppression devices are recommended for inductive loads, and each output supports a maximum 2 A inrush current for up to 100 ms.
Q7: What does the “E” revision indicate?
The “E” suffix identifies the hardware revision of the IC200MDL740. Revision E remains fully compatible with VersaMax systems while reflecting manufacturing, quality, and lifecycle improvements without changing the module’s operating characteristics.
Q8: What should be checked before replacing an IC200MDL740E module?
Before replacement, verify the VersaMax carrier compatibility, external 12/24 VDC field power supply, output wiring, load current requirements, PLC hardware configuration, and terminal assignments. Confirming these items helps ensure reliable installation and uninterrupted operation.
Tags
Packing & Delivery
We will use wear-resistant cartons to seal the boxes, and take photos for your confirmation before sealing. We will pack the boxes only after confirmation.
For express delivery, we will use DHL, UPS, TNT, FedEx and EMS.
Please rest assured that we have a deep cooperation with express delivery companies and can ensure that your goods are delivered to you in good condition.