Technical Specifications
| Item | Description |
|---|---|
| Model Number | KJ3222X1-BA1 |
| Input Type | Analog Input, 8 Channels, 4-20 mA with HART protocol |
| Module Type | Redundant, Series 2 |
| LocalBus Power Rating | 12 VDC @ 150 mA |
| Bussed Field Power | 24 VDC @ 300 mA |
| Field Circuit per Channel | 24 VDC @ 30 mA |
| Operating Temperature | -40°C to +70°C |
| Humidity Range | 5% to 95% Non-Condensing |
| Vibration Tolerance | 1 mm Peak-to-Peak (5–16 Hz); 0.5g (16–150 Hz) |
| Shock Tolerance | 10g, ½ Sinewave, 11 ms |
| Airborne Contaminants | ISA-S71.04-1985 Class G3 |
| Protection Rating | IP20 |
| Terminal Block Position | A1 |
| Hazardous Area Approvals | ATEX, IECEx, FM Class I Div 2 |
| Hot-Swap Capability | Supported with restrictions (one unit at a time, certain conditions) |
| Dimensions (W x H x D) | 107 x 41 x 105 mm |
| Weight | 0.18 kg |
FAQ
Frequently Asked Questions (FAQ)
Q1: What types of input does the KJ3222X1-BA1 support?
A1: It supports 8 channels of 4-20 mA analog input and is compatible with HART communication.
Q2: Is the module redundant?
A2: Yes, the KJ3222X1-BA1 is a Series 2 redundant card.
Q3: What are the power requirements of the module?
A3: The module uses 12 VDC (150 mA) for LocalBus, 24 VDC (300 mA) bussed field power, and 24 VDC (30 mA) per channel.
Q4: Can this module be used in hazardous areas?
A4: Yes, it is certified for ATEX, IECEx, and FM Class I Div 2 for use in Zone 2 hazardous environments.
Q5: Is hot-swapping supported for this module?
A5: Yes, but only one module at a time and specific conditions must be met for safe hot-swapping.
Q6: Does the module require periodic calibration?
A6: No, it is factory-calibrated and requires no user adjustment.
Q7: What are the environmental operating conditions for the module?
A7: It operates within -40°C to +70°C, 5% to 95% non-condensing humidity, and IP20 protection rating.
Q8: Is the module resistant to industrial contaminants?
A8: Yes, it complies with ISA-S71.04 G3 classification for harsh industrial conditions.