Manufacturer:Yokogawa
Product Number:AAR145
Product Type:RTD/POT Input Module
Origin:Japan
Dimensions:130 x 127.2 x 32.8 mm
Weight:0.3 kg
FAQ
Frequently Asked Questions (FAQ)
Q1: What types of sensors are supported by the AAR145 module?
A1: It supports RTD (e.g., Pt100) and potentiometer (POT) inputs, with independent configuration per channel.
Q2: Does the module offer electrical isolation?
A2: Yes, isolation exists between system and input, and also between channels.
Q3: How are RTD and POT inputs configured?
A3: Each channel can be independently configured as either RTD or POT input.
Q4: What is the maximum allowable wiring resistance?
A4: For RTD inputs, the wiring resistance must not exceed 150 Ω per wire.
Q5: What is the measurement accuracy of the module?
A5: The RTD input has an accuracy of ±150 mΩ, while POT input is ±0.2 % of full scale.
Q6: Is the module suitable for redundant system configurations?
A6: Yes, the AAR145 supports dual-redundant operation.
Q7: What is the data update period of the module?
A7: The data update period is 1 second, suitable for slowly changing signals like temperature.
Q8: Can the module be used in intrinsically safe zones?
A8: Yes, but only with an isolation barrier, not with a Zener barrier.