HIMA F60 AI 80 1 HIMatrix Module Technical Specifications
| Item | Specification |
|---|---|
| Module Name | HIMA F60 AI 80 1 Safety Analog Input Module |
| Number of Input Channels | 8 unipolar or 4 bipolar analog inputs |
| Input Type | Voltage: 0~±10 V; Current: 0~20 mA (via shunt) |
| Input Resistance | 1 MΩ |
| Voltage Measurement Accuracy (25°C) | ±0.1% of full scale |
| Safety-related Measurement Accuracy | ±1% of full scale |
| Digital Resolution | 12-bit A/D conversion |
| Sampling Time | Approx. 45 µs per channel |
| Value Refresh | Once per F60 cycle |
| Power Supply Voltage | 24 VDC (-15%…+20%) |
| Power Consumption | 24 VDC / 380 mA; 3.3 VDC / 150 mA |
| Installation Space | 6 RU, 4 HP |
| Dimensions | 150 x 140 x 80 mm |
| Weight | 0.24 kg |
| Operating Temperature | 0 ~ +60°C |
| Storage Temperature | -40 ~ +85°C |
| Protection Class | IP20 (per IEC/EN 61131-2) |
| Safety Certification Level | SIL3 (IEC 61508/61511/62061), SIL4 (EN 5012x) |
FAQ
FAQ
Q1: What types of input signals does the module support?
A1: It supports voltage (±10V) and current (0~20mA with external shunt resistors) signals.
Q2: What is the maximum measurement accuracy of the module?
A2: ±0.1% of full scale at 25°C; up to ±1% in safety-related applications.
Q3: Does the module provide electrical isolation?
A3: Yes, all analog inputs are galvanically isolated from the I/O bus.
Q4: Is the module suitable for railway or vibration-prone environments?
A4: Yes, the AI 8 014 variant is compliant with EN 61373 for railway use.
Q5: Can input channels be configured for bipolar measurement?
A5: Yes, the module allows configuring 8 channels as 4 bipolar inputs.
Q6: How does the module react in case of a fault?
A6: An error code will be set (>0), ERR LED lights up, and the system enters safe state.
Q7: In which slots can this module be installed?
A7: It can be installed in slots 3 to 8 of the F60 subrack.
Q8: Does the module support hot swapping?
A8: No, the module must be inserted or removed only when powered off.