Technical Specifications
| Parameter | Specification |
|---|---|
| Model | Honeywell RM7890A1015 (7800 SERIES Burner Control) |
| Power Supply Voltage | 120 Vac (+10% / -15%), 50/60 Hz ±10% |
| Power Consumption | 10 W maximum |
| Maximum Connected Load | 2000 VA |
| Fuse Requirement | 15 A maximum, type SC or equivalent, fast blow |
| Sequence Timing (Normal Op.) | Initiate: 10 s, PFEP: 4 or 10 s, Run: Continuous |
| Ignition Output | 120 Vac, 4.5 A |
| Pilot Valve Output | 120 Vac, up to 4 A at P.F. 0.5, 20 A inrush |
| Main Fuel Valve Output | 120 Vac, up to 4 A at P.F. 0.5, 20 A inrush |
| Alarm Output | 120 Vac, 1 A pilot duty |
| Ambient Operating Temperature | -40°C to +60°C |
| Ambient Storage Temperature | -40°C to +66°C |
| Humidity | 85% RH non-condensing |
| Vibration | 0.5G |
| Mounting | Q7800A panel mount or Q7800B wall/burner mount |
| Compatible Flame Amplifiers | R7847, R7848, R7861, R7886, etc. |
| Communication Options (optional) | ControlBus, ModBus, Network Interface Units |
| Diagnostic Features | Sequence status, fault codes, lockout history, flame signal strength |
| Dimensions | 127 x 127 x 133 mm |
| Weight | 0.83 kg (822 g) |