Technical Specifications
| Parameter | Specification |
|---|---|
| Model | Yokogawa AAI143-S00/K4A00 Analog Input Module |
| Input Channels | 16 (Isolated) |
| Input Signal | 4 to 20 mA |
| Allowable Input Current | 24 mA |
| Withstanding Voltage | 1500 V AC between input and system, 1 min |
| Input Resistance (Power ON) | 270 Ω (20 mA) to 350 Ω (4 mA) |
| Input Resistance (Power OFF) | 500 kΩ or more |
| Accuracy | ±16 µA |
| Data Update Period | 10 ms |
| Transmitter Power Supply | 19.0 V or higher (at 20 mA), 25.5 V or less (at 0 mA), 25 mA current limit |
| 2-wire/4-wire Transmitter Setting | Selectable per channel via setting pin |
| Temperature Drift | ±16 µA per 10 °C |
| Max Current Consumption | 230 mA (5 V DC), 540 mA (24 V DC) |
| External Connection | Pressure clamp terminal, MIL connector, KS cable |
| HART Communication | Supported |
| Dimensions (W × D × H) | 107.5 × 32.8 × 130 mm |
| Weight | 0.3 kg |
FAQ
FAQ
Q1: What type of input signals does the AAI143 module support?
A1: It supports isolated 4 to 20 mA DC current input signals.
Q2: How many input channels are available on the AAI143-S00/K4A00 module?
A2: The module provides 16 isolated input channels.
Q3: Is the AAI143 module compatible with HART communication?
A3: Yes, the module supports HART communication when used with the appropriate ER bus node unit and firmware.
Q4: Can this module be used with both 2-wire and 4-wire transmitters?
A4: Yes, each channel can be configured individually via setting pins to support either 2-wire or 4-wire transmitters.
Q5: What is the power supply range for the transmitter connected to this module?
A5: It supplies 19.0 V or higher at 20 mA, and 25.5 V or less at 0 mA, with a maximum current of 25 mA.
Q6: What is the input resistance of the module when powered on?
A6: The input resistance ranges from 270 Ω at 20 mA to 350 Ω at 4 mA.
Q7: What is the isolation voltage between the input and the system?
A7: It provides 1500 V AC isolation for one minute.
Q8: What are the physical dimensions and weight of the AAI143 module?
A8: The module measures 107.5 × 32.8 × 130 mm and weighs 0.3 kg.