Technical Specifications
| Parameter | Specification |
|---|---|
| Model | Honeywell RM7850A1019 |
| Series | 7800 SERIES |
| Control Type | Microprocessor-based burner control |
| Power Supply | 120 Vac (+10%/-15%), 50/60 Hz (±10%) |
| Ignition Attempts | 1 or 5 (model dependent) |
| Control Voltage | 115 to 120 Vac |
| Input Signals | Preignition Interlock, Low Fire Switch, High Fire Switch, Lockout Input |
| Output Ratings | Main/Pilot Valves, Fan Motor: 120 Vac, 4A @ PF=0.5, 20A inrush |
| Alarm Contact | 120 Vac, 1A pilot duty |
| Ignition Output | 120 Vac, 2A |
| Flame Signal Input | 136 to 220 Vac, current limited |
| Firing Rate Outputs | High/Low/Modulate/Common: 120 Vac, 0.5A @ PF=0.5 |
| Ambient Operating Temp. | -40°C to +60°C (-40°F to +140°F) |
| Storage Temperature | -40°C to +66°C (-40°F to +150°F) |
| Humidity | 85% RH continuous, non-condensing |
| Vibration | 0.5G |
| Power Consumption | Max. 10 W (Relay Module) |
| Mounting | Q7800A wiring subbase (panel mount) |
| Safety Certification | SIL3 Capable, EN298, FM approved |
| Communication (Optional) | Data ControlBus™, KDM Display Module |
| Dimensions (H x W x D) | 127 x 127 x 133 mm |
| Weight | 0.73 kg |
FAQ
FAQ
Q1: What type of fuel burners can the RM7850A1019 control?
A1: The RM7850A1019 is designed for use with gas, oil, or combination fuel burners in fully modulating applications.
Q2: What safety features does the RM7850A1019 provide?
A2: It includes dynamic self-check logic, interlock monitoring, tamper-resistant timing, and both high and low fire purge switch checks.
Q3: How many ignition attempts can the RM7850A1019 perform?
A3: It can be configured for either 1 or 5 ignition attempts depending on the model and system requirements.
Q4: Can the RM7850A1019 retain data after power loss?
A4: Yes, it uses non-volatile memory to retain sequence status and fault history after power loss.
Q5: Is a display module necessary for operation?
A5: The Keyboard Display Module (KDM) is optional but provides enhanced diagnostics, flame signal strength, and status information.
Q6: Can the module be reset remotely?
A6: Yes, remote reset is supported if the system installation meets the required safety standards.
Q7: What is the operating temperature range?
A7: The RM7850A1019 operates in environments from -40°C to +60°C.
Q8: What mounting base is used with this module?
A8: It mounts on a Q7800A wiring subbase, designed for panel-mounted applications.