Technical Specifications
| Parameter | Value |
|---|---|
| Article Number | 3BSE081637R1 |
| Redundancy | Yes |
| Processor Type | MPC866 |
| Clock Frequency | 133 MHz |
| Performance (1000 boolean ops) | 0.09 ms |
| Memory | 64 MB (51.389 MB available for application) |
| Flash Memory for Storage | Yes, 4 MB Flash PROM for firmware |
| Switch Over Time in Redundant Config. | Max 10 ms |
| No. of Applications per Controller | 32 |
| No. of Programs per Application | 64 |
| No. of Diagrams per Application | 128 |
| No. of Tasks per Controller | 32 |
| Number of Different Cycle Times | 32 |
| Cycle Time per Application Program | Down to 1 ms |
| Power Supply | 24 V DC (19.2–30 V DC) |
| Power Consumption (typ/max) | 210 mA / 360 mA |
| Power Dissipation | 5.1 W (max 8.6 W) |
| Redundant Power Supply Status Input | Yes |
| Built-in Backup Battery | Lithium 3.6 V |
| Clock Synchronization | 1 ms (via CNCP protocol) |
| Communication Modules on CEX Bus | 12 |
| I/O Capacity on Modulebus | Max 96 (single) / 84 (redundant) |
| Ethernet Channels | 2 (IEEE 802.3, 10 Mbit/s, RJ-45) |
| Control Network Protocol | MMS, IAC |
| RS-232C Interfaces | 2 (COM3 general, COM4 service) |
| Operating Temperature | +5 to +55 °C |
| Storage Temperature | -40 to +70 °C |
| Relative Humidity | 5–95% non-condensing |
| Protection Class | IP20 |
| Altitude | 2000 m |
| Certifications | CE, UL, cULus, ISA Secure, Marine (DNV-GL, ABS, BV, LR) |
| RoHS / WEEE Compliance | Yes |
| Dimensions (W × H × D) | 135 × 186 × 119 mm |
| Weight | 2.7 kg |
FAQ
FAQ
Q1: What is the processor type used in the ABB PM866AK02?
A1: It uses the MPC866 microprocessor.
Q2: Does the PM866AK02 support redundant operation?
A2: Yes, it supports full CPU redundancy for higher availability.
Q3: What is the maximum switch-over time in redundant mode?
A3: The maximum switch-over time is 10 milliseconds.
Q4: How much memory is available for user applications?
A4: Out of 64 MB total memory, 51.389 MB is available for applications.
Q5: What communication protocols are supported on the control network?
A5: It supports MMS (Manufacturing Message Service) and IAC (Inter Application Communication).
Q6: What is the maximum operating temperature range?
A6: The operating temperature range is from +5 °C to +55 °C.
Q7: How many Ethernet ports are built into the unit?
A7: The unit has two built-in Ethernet ports.
Q8: What are the physical dimensions and weight of the PM866AK02?
A8: The dimensions are 135 × 186 × 119 mm and the weight is 2.7 kg.
Tags
Packing & Delivery
We will use wear-resistant cartons to seal the boxes, and take photos for your confirmation before sealing. We will pack the boxes only after confirmation.
For express delivery, we will use DHL, UPS, TNT, FedEx and EMS.
Please rest assured that we have a deep cooperation with express delivery companies and can ensure that your goods are delivered to you in good condition.