Allen-Bradley 1420-V2P-ENT PowerMonitor 500 Power Meter – Technical Specifications and FAQ
Technical Specifications
| Parameter | Specification |
|---|---|
| Brand | Allen-Bradley / Rockwell Automation |
| Product Type | PowerMonitor 500 Multifunction Power Meter |
| Catalog Number | 1420-V2P-ENT |
| Lifecycle Status | Active |
| Maximum Metering Voltage | 600 VAC Line-to-Line |
| Nominal Voltage | 400 VAC Line-to-Neutral / 600 VAC Line-to-Line |
| Input Phase | Single-phase, two-phase or three-phase |
| Current Input | 5 A nominal, 6 A maximum (via CTs) |
| Frequency | 45–65 Hz |
| Communication | EtherNet/IP |
| Additional Protocol | Modbus TCP/IP |
| Relay Outputs | 2 configurable SPDT relay outputs |
| Output Functions | Pulse output, alarm output and communication-controlled output |
| Auxiliary Power Supply | 100–240 VAC, 48–62 Hz |
| Display | Built-in LCD, four rows of four digits |
| Measurement Functions | Voltage, current, frequency, active power, reactive power, apparent power and power factor |
| Energy Measurement | Imported/exported kWh and kVARh |
| Measurement Accuracy | 1.0% |
| Energy Accuracy | Class 1 kWh; Class 2 kVARh |
| Front Protection | IP65, NEMA 4X, NEMA 12 |
| Mounting | Panel mounting |
| Dimensions (W × H × D) | Module holder: 96 × 96 × 50 mm |
| Communication Module Dimensions | 89.5 × 63 × 20 mm |
| Maximum Depth Behind Panel | 81.7 mm |
| Weight | Approx. 400 g (including packing) |
FAQ
FAQ
Q1: What is the Allen-Bradley 1420-V2P-ENT?
A: It is a PowerMonitor 500 multifunction power meter designed for monitoring electrical energy consumption and power quality in industrial applications.
Q2: What is the maximum metering voltage?
A: It supports metering voltage up to 600 VAC line-to-line.
Q3: What current transformer input does it support?
A: It supports a nominal 5 A CT input, with a maximum current input of 6 A.
Q4: Does this model support Ethernet communication?
A: Yes. It supports EtherNet/IP communication and Modbus TCP/IP.
Q5: How many relay outputs does it have?
A: It provides two configurable SPDT relay outputs for alarms, pulse transmission or communication-controlled functions.
Q6: What electrical parameters can it measure?
A: It measures voltage, current, frequency, active power, reactive power, apparent power, power factor and electrical energy.
Q7: What is the difference between 1420-V2P and 1420-V2P-ENT?
A: The 1420-V2P-ENT version includes EtherNet/IP communication, whereas the standard 1420-V2P version does not include built-in communication.
Q8: What are the dimensions and weight?
A: The main module holder measures 96 × 96 × 50 mm, with a maximum depth behind the panel of 81.7 mm. The listed weight is approximately 400 g, including packing.
Tags
Packing & Delivery
We will use wear-resistant cartons to seal the boxes, and take photos for your confirmation before sealing. We will pack the boxes only after confirmation.
For express delivery, we will use DHL, UPS, TNT, FedEx and EMS.
Please rest assured that we have a deep cooperation with express delivery companies and can ensure that your goods are delivered to you in good condition.