Welcome to NewPLC!

Email

sales@bid-procurement.com

WhatsApp

+8613950166376

Honeywell 10209/2/1 Digital Output Module

Honeywell 10209/2/1 Digital Output Module

Release time:2025-04-17

Views:152

Payment Methods:T/T, PayPal, Western Union

Condition:New & In Stock

Shipping Port:Xiamen, China

Warranty:1 Year

Lead Time:1-3 Working Days

Certificate:COO

Courier partners:DHL, UPS, TNT, FedEx and EMS.

Business hours:7*24

Send Inquiry
Description
FAQ
Products Description
Honeywell 10209/2/1 Digital Output Module
Honeywell 10209/2/1 Digital Output Module
Honeywell 10209/2/1 Digital Output Module
Honeywell 10209/2/1 Digital Output Module
Company Information
E-mail sales@bid-procurement.com
Mobile +8613950166376
Whatsapp +8613950166376
WeChat 13950166376

Manufacturer:Honeywell

Product Number:10209/2/1

Product Type:Digital Output Module

Origin:USA

Dimensions:130 x 40 x 180 mm

Weight:0.65 kg


FAQ
Click to rate this post!
[Total: 0 Average: 0]

Frequently Asked Questions (FAQ)

Q1: How many output channels are available in the 10209/2/1 module?
A1: The module provides 16 digital output channels.

Q2: Are the outputs protected against short circuits?
A2: Yes, all outputs are solid-state source type and are short-circuit proof.

Q3: What is the maximum current each output can handle?
A3: Each output can drive up to 100 mA.

Q4: Can inductive loads be connected directly to the outputs?
A4: Yes, inductive loads such as relays can be connected. Each output includes a suppression diode for protection.

Q5: Does the module support fail-safe operation?
A5: No, the outputs are not tested and therefore should not be used in fail-safe applications.

Q6: What happens to the outputs if the system watchdog is triggered?
A6: All outputs are de-energized when the watchdog is activated or if the system shuts down.

Q7: What is the maximum allowable load capacitance per channel?
A7: Each channel supports a maximum load capacitance of 1 microfarad (µF).

Q8: What are the required supply voltages for the module to operate?
A8: The module requires 5 Vdc at 35 mA and 24 Vdc at 85 mA (excluding output load).