Honeywell FS-SDO-0824 Safe Digital Output Module

Honeywell FS-SDO-0824 Safe Digital Output Module

Release time:2025-08-18

Views:121

Payment Methods:T/T, PayPal, Western Union

Condition:New & In Stock

Shipping Port:Xiamen, China

Warranty:1 Year

Lead Time:1-3 Working Days

Certificate:COO

Courier partners:DHL, UPS, TNT, FedEx and EMS.

Business hours:7*24

Send Inquiry
Description
FAQ
Products Description
Honeywell FS-SDO-0824 Safe Digital Output Module
Honeywell FS-SDO-0824 Safe Digital Output Module
Honeywell FS-SDO-0824 Safe Digital Output Module
Honeywell FS-SDO-0824 Safe Digital Output Module
Company Information
E-mail sales@bid-procurement.com
Mobile +8613950166376
Whatsapp +8613950166376
WeChat 13950166376

Manufacturer:Honeywell

Product Number:FS-SDO-0824

Product Type:Safe Digital Output Module

Origin:USA

Dimensions:20.32 x 133.35 x 156 mm

Weight:0.7 kg


FAQ
Click to rate this post!
[Total: 0 Average: 0]

FAQ

  • Q1: What types of loads can the FS-SDO-0824 safely drive?
    A: It can drive resistive loads like lamps and inductive loads such as solenoids up to 13 W per channel, with suppression diodes included for inductive loads.

  • Q2: How does the module ensure safe operation for each output?
    A: Each output, including its suppression diode, is fully tested. The module also features secondary means of de-energizing to maintain safety even if the primary function fails.

  • Q3: What is the purpose of the secondary means of de-energizing (SMOD)?
    A: SMOD allows the watchdog and processor to de-energize outputs independently of the application logic, enhancing functional safety.

  • Q4: How are the outputs organized for diagnostic purposes?
    A: The eight outputs are split into two groups of four, and each group is independently monitored during the configured Diagnostic Test Interval.

  • Q5: What tests are performed during the Diagnostic Test Interval?
    A: The module tests the ability to de-energize each output, de-energize the group, detect crosstalk, and verify suppression diode function.

  • Q6: What is the maximum current each output can handle?
    A: Each output can handle up to 0.55 A safely, corresponding to a maximum load of 13 W.

  • Q7: Can this module be used in SIL-rated safety systems?
    A: Yes, the fully tested outputs and secondary de-energizing features make it suitable for SIL-compliant applications.

  • Q8: What are the physical dimensions and weight of the FS-SDO-0824?
    A: The module measures 20.32 × 133.35 × 156 mm and weighs 0.7 kg.