FAQ
Products Description
Yokogawa AAI135-H50 Analog Input Module
Yokogawa AAI135-H50 Analog Input Module
Yokogawa AAI135-H50 Analog Input Module
Yokogawa AAI135-H50 Analog Input Module
Company Information
E-mail sales@bid-procurement.com
Mobile +8613950166376
Whatsapp +8613950166376
WeChat 13950166376

Manufacturer:Yokogawa

Product Number:AAI135-H50

Product Type:Analog Input Module

Origin:Japan

Dimensions:107.5×32.8×130 mm

Weight:0.3 kg


FAQ
Click to rate this post!
[Total: 0 Average: 0]

Frequently Asked Questions (FAQ)

Q1: What is the primary function of the AAI135-H50 module?
A1: The AAI135-H50 is an 8-channel analog input module designed to receive 4 to 20 mA signals while providing isolation and supporting HART communication.

Q2: Does this module support redundant configurations?
A2: Yes, the AAI135-H50 can be used in dual-redundant configurations for high-reliability applications.

Q3: What is the isolation voltage rating of this module?
A3: The module features 500 VAC isolation between the input and system, as well as between input channels.

Q4: Can this module be used in hazardous environments?
A4: The module itself is designed for industrial use but must be installed in an appropriate enclosure to meet hazardous area requirements.

Q5: What type of connectors does the module use?
A5: The AAI135-H50 supports pressure clamp terminals, MIL connectors, and dedicated KS1 cables.

Q6: What is the update rate of the module?
A6: The data update period for the AAI135-H50 is 10 ms, ensuring real-time signal processing.

Q7: What is the operating temperature range of this module?
A7: The operating temperature range is typically from 0°C to 55°C, depending on system requirements.

Q8: Does this module support HART communication?
A8: Yes, the AAI135-H50 supports HART protocol for advanced diagnostics and remote configuration.

Q9: How much power does this module consume?
A9: The module consumes 360 mA at 5 V DC and 450 mA at 24 V DC.

Q10: What are the dimensions and weight of this module?
A10: The AAI135-H50 measures 107.5 × 32.8 × 130 mm and weighs 0.3 kg.