Products Description




| Company Information | |||
| [email protected] | |||
| Mobile | +8613950166376 | ||
| +8613950166376 | |||
| 13950166376 |

Technical Specifications
| Specification | Details |
|---|---|
| Product Name | Allen-Bradley 1756-OA16I ControlLogix Isolated Digital AC Output Module |
| Module Type | Digital AC Output Module (Individually Isolated) |
| Series | ControlLogix |
| Number of Outputs | 16 individually isolated channels |
| Output Voltage Range | 74–265 VAC, 47–63 Hz |
| Nominal Output Voltage | 120 VAC / 240 VAC |
| Output Current | 2 A per point @ 30 °C, 1 A per point @ 60 °C |
| Minimum Load Current | 10 mA per point |
| Surge Current | 20 A for 43 ms per point |
| Isolation Voltage | 250 V continuous (output-to-output & backplane) |
| Backplane Current (5.1 VDC) | ~300 mA |
| Backplane Current (24 VDC) | ~2.5 mA |
| Power Dissipation | ~5.5 W @ 60 °C |
| Output Delay Time | ~9.3 ms (60 Hz), ~11 ms (50 Hz) |
| Output Type | Triac (AC output) |
| Connection Type | Removable Terminal Block (1756-TBCH / 1756-TBS6H) |
| Mounting | ControlLogix chassis slot |
| Operating Temperature Range | 0 °C to 60 °C |
| Storage Temperature Range | −40 °C to 85 °C (typical) |
| Relative Humidity (Non-condensing) | 5 % to 95 % |
| Enclosure Type | Open-type (chassis mounted) |
| Dimensions (H × W × D) | 300 mm × 38.1 mm × 111.25 mm |
| Weight | ~0.40 kg (typical shipping estimate) |
FAQ
FAQ
Q1: What is the key difference between 1756-OA16 and 1756-OA16I?
The 1756-OA16I provides individual isolation per output channel, improving protection and reducing interference.
Q2: How many output channels are available?
It has 16 individually isolated AC output channels.
Q3: What voltage range does the module support?
It operates from 74 VAC to 265 VAC at 47–63 Hz.
Q4: What types of loads can it control?
It is suitable for AC loads such as relays, contactors, lamps, and solenoids.
Q5: What is the maximum output current per channel?
Up to 2 A per point at 30 °C, derated to 1 A at 60 °C.
Q6: How is wiring connected to the module?
Through a removable terminal block such as 1756-TBCH or 1756-TBS6H.
Q7: What are the typical response times?
Switching delay is about 9–11 ms depending on frequency.
Q8: What are the physical size and weight?
The module measures 300 mm × 38.1 mm × 111.25 mm and weighs about 0.40 kg.