Manufacturer:GE
Product Number:IC200UEX012
Product Type:VersaMax Micro Expansion Unit
Origin:USA
Dimensions:90 × 160 × 75 mm
Weight:0.46 kg
FAQ
FAQ
Q1: What is the GE Fanuc IC200UEX012 used for?
The IC200UEX012 is an expansion I/O unit that increases the digital input and relay output capacity of VersaMax Micro PLC systems. It is commonly used in machine automation, material handling, packaging, and process control applications.
Q2: How many inputs and outputs does the IC200UEX012 provide?
The module provides 8 digital 24 VDC inputs and 6 normally open relay outputs, for a total of 14 I/O points.
Q3: What types of input signals are supported?
The eight digital inputs accept 24 VDC positive or negative logic signals, making the module compatible with pushbuttons, limit switches, proximity sensors, and other industrial input devices.
Q4: What loads can the relay outputs control?
Each relay output is rated for 2 A and can switch 5–30 VDC or 5–250 VAC loads. Typical applications include motor starters, solenoid valves, relays, contactors, and indicator lamps.
Q5: Does the IC200UEX012 include an auxiliary power supply?
Yes. The module includes an isolated 24 VDC auxiliary output rated at 200 mA, which can be used to power input circuits and low-power field devices.
Q6: How many expansion units can be connected to a VersaMax Micro PLC?
Depending on the PLC CPU model, the system supports up to four expansion units, allowing additional digital and analog I/O to be added as application requirements grow.
Q7: Does the IC200UEX012 provide electrical isolation?
Yes. The module provides 1500 VAC RMS isolation between the field wiring and the PLC logic, as well as 500 VAC RMS isolation between input groups, improving noise immunity and system protection.
Q8: What should be checked before replacing an IC200UEX012 module?
Before replacement, verify the VersaMax Micro CPU compatibility, 24 VDC power supply, field wiring, relay load ratings, expansion cable connections, and PLC configuration to ensure the replacement module operates correctly.