Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | GE Fanuc (now Emerson Automation) |
| Product Model | IC693MDL930D |
| Product Type | Isolated Relay Output Module |
| Series | Series 90-30 PLC |
| Function | Provides relay switching outputs for controlling AC/DC field devices from the PLC |
| Output Type | Normally Open (N.O.) Relay Contact Output |
| Number of Output Points | 8 points |
| Output Configuration | 8 individually isolated relay outputs |
| Rated Voltage | 24 VDC, 120/240 VAC nominal |
| Operating Voltage Range | 5–30 VDC / 5–250 VAC, 50/60 Hz |
| Maximum Output Current | 4 A resistive load per point |
| Pilot Duty Current | 2 A per point |
| Maximum Module Current | 20 A maximum (UL installation) |
| Minimum Load Current | 10 mA |
| Maximum Inrush Current | 5 A maximum |
| Output Contact Type | Form A (SPST-NO) relay contacts |
| Isolation Voltage | 1500 VAC for 1 minute (field side to logic side) |
| Point-to-Point Isolation | 1500 VAC for 1 minute |
| Continuous Isolation Rating | 250 VAC continuous |
| ON Response Time | 15 ms maximum |
| OFF Response Time | 15 ms maximum |
| Backplane Power Consumption | 6 mA from 5 VDC bus |
| Relay 24 VDC Bus Consumption | 70 mA (all outputs ON) |
| LED Indicators | Individual output status LEDs |
| Terminal Connection | 20-position removable screw terminal block |
| Compatible Baseplates | GE Fanuc Series 90-30 5-slot and 10-slot baseplates |
| Installation Position | Any available I/O slot |
| Compatible Systems | GE Fanuc Series 90-30 PLC |
| Mounting Method | Rack-mounted PLC module |
| Operating Temperature | 0°C to +60°C (32°F to +140°F) |
| Storage Temperature | -40°C to +85°C (-40°F to +185°F) |
| Relative Humidity | 5–95% RH (non-condensing) |
| Dimensions (H × W × D) | Approx. 127 × 51 × 127 mm (5.0 × 2.0 × 5.0 in.) |
| Weight | Approx. 0.30 kg (0.66 lb) |
| Hardware Revision | D |
| Product Status | Legacy Product |
| Warranty | 12 Months |
FAQ
FAQ
Q1: What is the GE Fanuc IC693MDL930D used for?
The IC693MDL930D is used to provide relay-based switching outputs from a Series 90-30 PLC to external field devices such as motors, contactors, valves, and control lamps.
Q2: How many outputs does the IC693MDL930D provide?
The module provides 8 isolated relay output points, with each relay output operating independently.
Q3: What voltage levels can the IC693MDL930D switch?
The module supports 5–30 VDC and 5–250 VAC at 50/60 Hz, making it suitable for a wide range of industrial loads.
Q4: What is the maximum current rating of each output?
Each relay output can handle up to 4 A resistive load per point and up to 2 A for pilot-duty applications.
Q5: Is the IC693MDL930D electrically isolated?
Yes. The module provides isolation between the field side and PLC logic side, with up to 1500 VAC isolation for one minute.
Q6: What type of relay contacts are used in the IC693MDL930D?
The module uses Form A normally open (SPST-NO) relay contacts, suitable for switching external loads.
Q7: Which PLC systems are compatible with the IC693MDL930D?
The IC693MDL930D is designed for use with GE Fanuc Series 90-30 PLC systems and can be installed in standard Series 90-30 I/O slots.
Q8: What should be checked before replacing an IC693MDL930D module?
Before replacement, verify the Series 90-30 rack compatibility, output wiring, load voltage and current ratings, terminal connections, PLC configuration, and relay output requirements to ensure proper operation.