Technical Specifications
| Parameter | Specification |
|---|---|
| Model | IC695CHS012 |
| Product Type | RX3i 12-Slot Universal Backplane |
| Number of Slots | 12 |
| Bus Type | Dual Bus: PCI-based and Serial |
| Slot 0 Compatibility | IC695 Power Supply only |
| Expansion Slot | Slot 12, for IC695LRE001 Serial Expansion Module only |
| Compatible Modules | IC695, IC694, IC693 series modules |
| Grounding | Integrated grounding bar with M3 screw support |
| Terminal Strip | TB1 for isolated +24VDC input (terminals 7 and 8) |
| Slot Labeling | Printed on backplane for module configuration reference |
| Mounting Orientation | Horizontal mounting only |
| Minimum Clearance for Cooling | 102 mm (4 inches) on all sides |
| Operating Conditions | Must be enclosed in protective housing (IP20 or NEMA Type 1) |
| Dimensions (W x L x H) | 141.48 x 457.45 x 147.32 mm |
| Weight | 1.58 kg |
FAQ
Frequently Asked Questions (FAQ)
Q1: How many modules can be installed on the IC695CHS012 base?
A1: Up to 12 modules can be installed, with slot 0 reserved for a power supply and slot 12 reserved for expansion.
Q2: Can the IC695CHS012 support both PCI and Serial modules?
A2: Yes, each slot (except slot 0 and 12) has dual connectors for PCI-based and serial modules.
Q3: Can the CPU be installed in any slot?
A3: The CPU can be installed in any slot except slot 12. CPU modules occupy two slots.
Q4: Is hot-swapping supported for I/O modules?
A4: Yes, as long as the hot installation procedure is strictly followed per system manual GFK-2314.
Q5: What type of power supplies are compatible with slot 0?
A5: Only IC695 power supplies are compatible. IC694 and IC693 power supplies are not supported.
Q6: How is grounding handled in the base?
A6: A grounding bar is integrated into the backplane, allowing module shields to be grounded via M3 screws.
Q7: What precautions are required for hazardous location installation?
A7: Ensure power is off before wiring or module replacement, and only use in Class I, Division 2 approved areas.
Q8: Can AC power supplies be used when the CPU is installed in slot 1?
A8: No, if the CPU is in slot 1, only a single-width DC power supply can be used in slot 0. AC supplies must be placed elsewhere.