Technical Specifications
| Parameter | Description |
|---|---|
| Module Model | IC695CMM002 |
| Number of Serial Ports | 2 independent isolated serial ports |
| Serial Port Type | RS-232 or RS-485/422 (2-wire or 4-wire) |
| Connector Type | RJ-45 |
| Supported Baud Rates | 1200, 2400, 4800, 9600, 19.2K, 38.4K, 57.6K, 115.2K bps |
| Data Bits | 7 or 8 |
| Stop Bits | 1 or 2 |
| Parity | Even, Odd, None |
| Flow Control | Hardware (RTS/CTS) or None |
| Port Isolation | 250VAC continuous to backplane/ground; 1500VAC for 1 min |
| Channel-to-Channel Isolation | 500VDC continuous, 710VDC for 1 minute |
| Input Impedance | RS-485/422: >96 kΩ; RS-232: 3–7 kΩ |
| Max Overvoltage | ±25V |
| Power Consumption | 3.3V @ 0.7A, 5V @ 0.115A |
| LEDs | Module OK, Port Fault, Port Status (2 ports) |
| Supported Protocols | MODBUS Master/Slave, Serial I/O, CCM Slave, DNP3 Master/Slave (version dependent) |
| Operating Temperature | 0°C to +60°C |
| Installation Slot | RX3i Universal Backplane |
| Hot-Swap Support | Supported |
| Dimensions | 134.6 x 165.1 x 30 mm |
| Weight | 0.25 kg |
| Certifications | CE, UL/CUL 508/1604, ATEX |
FAQ
Frequently Asked Questions (FAQ)
Q1: How many serial ports does the IC695CMM002 module support?
A1: It supports two independent and isolated serial ports.
Q2: What communication protocols are supported?
A2: It supports MODBUS Master/Slave, Serial I/O, CCM Slave (v1.10+), and DNP3 Master/Slave (v1.20+).
Q3: Is hot-swapping supported?
A3: Yes, hot insertion and removal are supported as per RX3i system manual instructions.
Q4: Can DNP3 protocol read multiple group objects in a single request?
A4: No, only the first group object is read. Multiple requests must be issued for different groups.
Q5: Is termination required for RS-485?
A5: Yes, termination is needed if the module is the first or last device on the RS-485 network.
Q6: What is the electrical isolation rating?
A6: Port-to-backplane isolation is 250VAC continuous, and port-to-port is 500VDC continuous.
Q7: Is it compatible with Series 90-30 CPU363?
A7: Yes, compatible through proper RJ-45 wiring.
Q8: What baud rates are available?
A8: Supports 1200 to 115200 bps across eight selectable baud rates.