Technical Specifications
| Parameter | Description |
|---|---|
| Product Range | Modicon Quantum Automation Platform |
| Product or Component Type | Power Supply Module |
| Power Supply Type | Summable |
| Input Voltage | 48…60 V DC |
| Input Current | 3800 mA |
| Inrush Current | 14 A at 40 V |
| Maximum Input Power Interruption | 13 ms at 48 V |
| Associated Fuse Rating | 2 A, time-lag |
| Output Voltage | 5.1 V DC |
| Power Supply Output Current | 8 A summable |
| Output Overvoltage Protection | Internal |
| Output Overload Protection | Internal |
| Power Dissipation | 15.6 W |
| Alarm Output | 1 NC contact, 6 A, 220 V for power supply fault |
| Local Signalling | 1 LED (green) for power (PWR OK) |
| Marking | CE |
| Module Format | Standard |
| Net Weight | 0.65 kg |
| Dimensions | 103.9 × 40.3 × 250 mm |
| Protective Treatment | Conformal coating Humiseal 1A33 |
| Standards | CSA C22.2 No 142, UL 508 |
| Product Certifications | cUL |
| Electrostatic Discharge Resistance | 4 kV contact, 8 kV air, conforming to IEC 801-2 |
| Electromagnetic Field Resistance | 10 V/m, 80–2000 MHz, conforming to IEC 801-3 |
| Ambient Air Temperature for Operation | 0…60 °C |
| Ambient Air Temperature for Storage | -40…85 °C |
| Relative Humidity | 95% non-condensing |
| Operating Altitude | ≤ 5000 m |
FAQ
FAQ
Q1: What is the input voltage range supported by this module?
A1: The supported input voltage range is 48 to 60 V DC.
Q2: What is the maximum output current of the module?
A2: The output current is 8 A and it is summable.
Q3: Does the module provide overload protection?
A3: Yes, it includes internal output overload protection.
Q4: What type of alarm output does this module have?
A4: It offers one normally closed (NC) contact, 6 A, 220 V, for power fault indication.
Q5: What are the physical dimensions of the module?
A5: The dimensions are 103.9 × 40.3 × 250 mm.
Q6: What is the inrush current capability of this module?
A6: It can handle up to 14 A at 40 V.
Q7: Does the module offer electromagnetic interference resistance?
A7: Yes, it conforms to IEC 801-3 and can withstand 10 V/m (80–2000 MHz).
Q8: What is the acceptable ambient operating temperature range?
A8: The module operates within 0 to 60 °C ambient temperature.
Tags
Packing & Delivery
We will use wear-resistant cartons to seal the boxes, and take photos for your confirmation before sealing. We will pack the boxes only after confirmation.
For express delivery, we will use DHL, UPS, TNT, FedEx and EMS.
Please rest assured that we have a deep cooperation with express delivery companies and can ensure that your goods are delivered to you in good condition.