Products Description




| Company Information | |||
| [email protected] | |||
| Mobile | +8613950166376 | ||
| +8613950166376 | |||
| 13950166376 |

Technical Specifications
| Parameter | Specification |
|---|---|
| Product Model | Honeywell RM7800M1037 |
| Series | 7800 Series |
| Control Type | Microprocessor-based integrated burner control |
| Voltage Input | 120 Vac (+10/-15%), 50 or 60 Hz (±10%) |
| Power Consumption | RM7800: Max 10 W, Display Module: Max 3 W |
| Max Connected Load | 2000 VA |
| Fuse Rating | 15A Fast Blow (Type SC or equivalent) |
| Operating Temperature | -40°C to 60°C (-40°F to 140°F) |
| Storage Temperature | -40°C to 66°C (-40°F to 150°F) |
| Humidity | 85% RH non-condensing |
| Vibration Resistance | 0.5G |
| Flame Failure Response Time | 0.8 to 3.0 seconds (based on amplifier type) |
| Mounting Options | Q7800A (panel), Q7800B (wall or burner) |
| Communication Options | Modbus™, Data ControlBus™ Module |
| Safety Compliance | SIL 3 capable, UL listed, CSA certified, FM approved |
| Display | 2×20 VFD (Vacuum Fluorescent Display), 26-LED optional annunciator |
| Memory | Non-volatile for history, fault logs, and settings |
| Dimensions | 127 x 127 x 133 mm |
| Weight | 0.83 kg (1 lb 13 oz) |
FAQ
FAQ
Q1: What type of applications is the RM7800M1037 designed for?
A1: It is designed for single-burner, automatically fired systems using gas, oil, or combination fuels.
Q2: Does the RM7800M1037 support Modbus communication?
A2: Yes, it supports Modbus communication via an optional S7810M1003 module.
Q3: What safety features are built into the RM7800M1037?
A3: It includes dynamic self-checks, tamper-resistant logic, interlock verification, and flame signal monitoring.
Q4: What is the purpose of the Keyboard Display Module?
A4: The KDM provides sequence status, fault diagnostics, and reset capabilities locally or remotely.
Q5: Can the RM7800M1037 store operating history and fault records?
A5: Yes, it has non-volatile memory that logs up to six fault events, operating hours, and cycle counts.
Q6: What is the post purge timing capability of the RM7800M1037?
A6: The post purge time is adjustable up to 60 minutes and comes preset at 15 seconds.
Q7: Is remote reset functionality available?
A7: Yes, remote reset is supported via an optional S7820A1007 Remote Reset Module.
Q8: What is the recommended flame detection method for this model?
A8: It supports rectification, ultraviolet (self-check and non-self-check), and infrared detection using compatible amplifiers and sensors.
Tags
Packing & Delivery
We will use wear-resistant cartons to seal the boxes, and take photos for your confirmation before sealing. We will pack the boxes only after confirmation.
For express delivery, we will use DHL, UPS, TNT, FedEx and EMS.
Please rest assured that we have a deep cooperation with express delivery companies and can ensure that your goods are delivered to you in good condition.